Bryant 355CAV installation instructions Winter Design Temperature Ambient

Models: 355CAV

1 60
Download 60 pages 10.1 Kb
Page 39
Image 39

Table 6 – Maximum Allowable Exposed Vent Pipe Length (Ft / M) with Insulation in

Winter Design Temperature Ambient*

UNIT SIZE

WINTER DESIGN

MAXIMUM PIPE

 

 

INSULATION THICKNESS†

 

 

 

TEMPERATURE

DIAMETER (IN.)

 

0

3/8

1/2

3/4

1

 

 

 

 

 

 

042060

20_F / -6.7_C

2

30

/ 9.1

55 / 16.8

61 / 18.6

70 / 21.3

70 / 21.3

 

 

0_F / -17.8_C

2

16

/ 4.9

33 / 10.1

38 / 11.6

46 / 14.0

53 / 16.2

 

 

 

-20_F / -28.9_C

2

9 / 2.7

23 / 7.0

26 / 7.9

33 / 10.1

38 / 11.6

 

 

042080

20_F / -6.7_C

2

37 / 11.2

65 / 19.8

70 / 21.4

70 / 21.3

70 / 21.3

 

 

0_F / -17.8_C

2

20

/ 6.1

39 / 11.9

45 / 13.7

55 / 16.8

63 / 19.2

 

 

060080

 

 

-20_F / -28.9_C

2

11

/ 3.4

27 / 8.3

31 / 9.4

39 / 11.9

45 / 13.7

 

 

 

 

 

060100

20_F / -6.7_C

2-1/2

41 / 12.5

70 / 21.3

70 / 21.3

70 / 21.3

70 / 21.3

 

 

0_F / -17.8_C

2-1/2

21

/ 6.4

42 / 12.8

48 / 14.6

59 / 18.0

68 / 20.7

 

 

 

-20_F / -28.9_C

2-1/2

11

/ 3.4

28 / 8.5

33 / 10.1

41 / 12.5

49 / 14.9

 

 

060120

20_F / -6.7_C

3

49 / 14.9

70 / 21.3

70 / 21.3

70 / 21.3

70 / 21.3

 

 

0_F / -17.8_C

3

26

/ 7.9

51 / 15.5

58 / 17.7

70 / 21.3

70 /21.3

 

 

 

-20_F / -28.9_C

3

15

/ 4.6

35 / 10.7

40 / 12.2

50 / 15.2

59 / 18.0

 

 

* Pipe length (ft/m)

specified for maximum pipe

lengths located in unconditioned

spaces. Pipes

located in unconditioned space cannot exceed total allowable

 

 

pipe length as specified in Table ?.

 

 

 

 

 

 

 

 

 

Insulation thickness based on R value of 3.5 per in.

 

 

 

 

 

 

 

355CAV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Page 39