2.Locate heat tape between sides of condensate trap back. (See Fig. 46.)
3.Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig. 46.)
4.Wrap field drain pipe with remaining heat tape, approximately 1 wrap per ft.
5.When using
START-UP, ADJUSTMENT AND SAFETY
CHECK
Step 1 — General
1.Furnace must have a
NOTE: Proper polarity must be maintained for
2.Thermostat wire connections at terminals R, W/W1, G, and Y/Y2 must be made at
3.Natural gas service pressure must not exceed 0.5 psig (14- in. wc), but must be no less than 0.16 psig
4.Blower access panel must be in place to complete
!CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
These furnaces are equipped with a manual reset limit switch in burner box. This switch opens and shuts off power to the gas valve if an overheat condition (flame rollout) occurs in burner enclosure. Correct inadequate
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
Step 2 — Select Setup Switch Positions
Air Conditioning (A/C) Setup Switches
The air conditioning setup switches are used to match furnace airflow to cooling unit used.
To set the desired cooling airflow:
1.Remove main furnace door and blower access panel.
2.Locate A/C setup switches on furnace control. (See Fig. 33.)
3.Determine air conditioning tonnage used.
4.Use Fig. 47 or wiring schematic to determine proper setup position of A/C switches. (See Fig. 48 and Fig. 49.)
NOTE: Excessive airflow caused by improper A/C switch setup may cause condensate blowoff in cooling mode.
5. Replace main furnace door and blower access panel.
NOTE:
Continuous Fan (CF) Setup Switches
The CF setup switches are used to select desired airflow when thermostat is in continuous fan mode or to select
continuous fan airflow or
1.Remove main furnace door and blower access panel.
2.Locate CF setup switches on furnace control. (See Fig. 33.)
3.Determine desired continuous fan airflow or
4.Use Fig. 47 or wiring schematic to determine proper setup position of CF switches. (See Fig. 48 and Fig. 49.)
5.Replace main furnace door and blower access panel.
AIR CONDITIONING (A/C) OR
AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON (SETUP SWITCH
SETUP SWITCH SW3 POSITIONS
MODEL
SIZE
060, 3.5T080 | DEF. | 525 2 | 700 |
| 875 |
| 1050 1 | 1225 | 1225 | 1225 | ||||||||||||||||
5T080, 100 | DEF. | 700 2 | 875 |
| 1050 | 1225 | 1400 | 1750 1 | 1750 | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
120 | DEF. | 700 |
| 875 2 | 1050 | 1225 | 1400 | 1750 1 | 2100 | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BASED ON 400 CFM/TON (SETUP SWITCH |
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
MODEL |
|
|
|
|
|
| SETUP SWITCH SW3 POSITIONS |
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SIZE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
060, 3.5T080 | DEF. | 600 2 | 800 |
| 1000 | 1200 1 | 1400 | 1400 | 1400 | |||||||||||||||||
|
|
|
|
|
|
|
|
| ||||||||||||||||||
5T080, 100 | DEF. | 800 2 | 1000 | 1200 | 1400 | 1600 | 2000 1 | 2000 | ||||||||||||||||||
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
120 | DEF. | 800 |
| 1000 2 | 1200 | 1400 | 1600 | 2000 1 | 2100 | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3.SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
A07424
Fig. 47 - A/C or CF Airflow Selection Chart Based on 350
and 400 CFM/Ton
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to meet the application requirements. To set these setup switches for the appropriate requirement:
1.Remove main furnace door and blower access panel.
2.Locate setup switches on furnace control. (See Fig. 33.)
3.See Table 9 for setup switch description. (See Fig. 48 and Fig. 49.)
4.Replace main furnace door and blower access panel.
NOTE: If a bypass humidifier is used, setup switch
NOTE: If modulating dampers are used, blower motor automatically compensates for modulating dampers.
Additional Setup Switches (SW4)
The furnace control has 3 additional setup switches labeled SW4. (See Fig. 33.) Setup switch
1. Remove main furnace door and blower access panel.
355CAV
43