![Check Safety Controls](/images/new-backgrounds/54127/54127117x1.webp)
NOTE: When using an electronic thermostat, set cycle rate for 3 | 2. | Remove control access door and disconnect inducer motor | ||||
cycles per hr. |
|
| ||||
3. Return setup switch | 3. | Turn on |
| |||
thermostat on subbase. | 4. | Set thermostat to “call for heat.” When pressure switches | ||||
Check Safety Controls |
| are functioning properly, status code 42 will flash on fur- | ||||
This section covers the safety controls that must be checked |
| nace control approximately 20 sec after thermostat switch | ||||
| is closed. If either a status code 31 or 32 is flashed when | |||||
before the installation is complete. The flame sensor, gas valve, |
| |||||
| inducer motor is disconnected, the furnace will shut itself | |||||
and pressure switches were all checked in the |
| |||||
| down | immediately. | Determine the reason | pressure | ||
section as part of normal operation. |
| |||||
| switches did not function properly and correct the condi- | |||||
Check Primary Limit Control |
| |||||
| tion. |
|
|
| ||
This control shuts off the gas control system and energizes the |
|
|
|
| ||
5. | Turn off |
| ||||
| ||||||
6. | Reconnect inducer motor wire harness. Reinstall furnace | |||||
1. The recommended method of checking this limit control is | ||||||
| access door. |
|
| |||
to gradually block off return air after furnace has been op- |
|
|
| |||
7. | Turn on |
| ||||
erating for a period of at least 5 minutes. |
| |||||
8. | Reset thermostat to desired temperature. |
| ||||
2. As soon as limit control has shut off burners, a status code |
| |||||
|
| CHECKLIST |
| |||
33 will appear on furnace control. |
|
|
| |||
3. The | 1. | Put away tools and instruments. Clean up debris. |
| |||
normal air circulation. | 2. | Verify flame rollout manual reset switch has continuity. | ||||
By using this method to check the limit control, it can be | ||||||
3. | Verify | that blower and | main access doors are | properly | ||
established that the limit is functioning properly and the furnace | ||||||
| installed. |
|
| |||
will operate safely if there is a restricted |
|
|
| |||
4. | Cycle test furnace with room thermostat. |
| ||||
failure. If the limit control does not function during this test, the |
| |||||
5. | Check operation of accessories per manufacturer’s instruc- | |||||
cause must be determined and corrected. | ||||||
Check Pressure Switches |
| tions. |
|
|
| |
6. | Review User’s Manual with owner. |
| ||||
This control proves operation of the draft inducer. Check switch |
| |||||
7. | Leave literature packet near furnace. |
| ||||
operation as follows: |
| |||||
|
|
|
|
|
1. Turn off
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT
EXAMPLE: | 5.0 AMPS ON AMMETER | = | 0.5 AMPS FOR THERMOSTAT | |
10 TURNS AROUND JAWS | ANTICIPATOR SETTING | |||
|
|
A96316
Fig. 63 - Amp Draw with Ammeter
355CAV
59