1.Disconnect collector box pressure tube (pink label) attached to High Pressure Switch.
2.Use smaller diameter tube
3.Route extended tube:
a.Behind inducer housing.
b.Between blower shelf and inducer housing.
4.Determine appropriate lenght, cut, and reconnect tube to High Pressure Switch connections labeled COLLECTOR BOX.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
!CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A
HORIZONTAL RIGHT
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.
!CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box
Condensate Trap Location
| PLUG |
COLLECTOR BOX | COLLECTOR BOX |
DRAIN TUBE (BLUE) | TUBE (GREEN) |
| COLLECTOR BOX TUBE (PINK) |
CAP | AUXILIARY “J” BOX RELOCATED HERE |
|
COLLECTOR BOX | CONDENSATE | |
TRAP |
| |
DRAIN TUBE (BLUE & |
| |
| 355CAV | |
WHITE STRIPED) |
| |
INDUCER HOUSING |
| |
(MOLDED) DRAIN |
|
|
TUBE (VIOLET) |
|
|
COLLECTOR BOX |
|
|
EXTENSION TUBE |
|
|
|
|
A07279
Fig. 14 - Horizontal Right Tube Configuration
The condensate trap must be removed from the
To relocate condensate trap from the blower shelf to desired location, perform the following:
1.Remove three tubes connected to condensate trap.
2.Remove trap from blower shelf by gently pushing tabs inward and rotaing trap.
!WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
3.Install casing hole filler cap
4.Install condensate trap into
5.Fill unused condensate trap casing holes with plastic filler caps
LEVEL |
| (0″) | FRONT |
| FRONT |
|
| ||||
|
| ||||
|
| ||||
TO |
| MIN 1⁄4″ | |||
1⁄2″ MAX |
| TO | |||
|
|
|
| 1⁄2″ MAX | |
UPFLOW OR DOWNFLOW |
| HORIZONTAL |
A02146
Fig. 15 - Proper Condensate Drainage
13