Bryant 355CAV Condensate Trap Alternate Upflow Orientation, Carbon Monoxide Poisoning Hazard

Models: 355CAV

1 60
Download 60 pages 10.1 Kb
Page 8
Image 8
Fig. 6 - Condensate Trap

355CAV

BLOWER SHELF

FURNACE

CONDENSATE

 

 

 

 

 

 

 

DOOR

 

 

 

 

 

 

 

TRAP

 

 

 

 

 

 

CONDENSATE

 

FURNACE

 

 

 

 

 

 

 

 

 

TRAP (INSIDE)

 

FURNACE

 

DOOR

FURNACE

 

 

 

 

 

 

 

SIDE

 

 

 

 

SIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 78

(124mm)

4

 

 

 

 

 

 

 

 

 

5 3 4 (146mm)

 

5 3 4

(146mm)

 

 

 

 

 

 

 

4

 

 

 

FIELD

26 1 4

11 2

 

FIELD

26 1 4

3

4

 

 

 

(667mm)

(19mm)

 

 

DRAIN

(667mm)

(38mm)

 

DRAIN

 

 

 

 

ALTERNATE DRAIN

CONN

 

CONN

 

 

 

 

 

 

 

 

 

 

 

TUBE LOCATION

SIDE VIEW

FRONT VIEW

 

 

END VIEW

FRONT VIEW

 

CONDENSATE TRAP

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN TUBE LOCATION

DOWNFLOW AND ALTERNATE

 

 

HORIZONTAL

 

 

 

 

 

 

 

 

 

UPFLOW APPLICATIONS

EXTERNAL UPFLOW APPLICATIONS

 

APPLICATIONS

 

 

 

SLOT FOR SCREW

 

 

 

 

 

 

 

 

 

HORIZONTAL

 

 

 

 

 

 

 

 

 

APPLICATION

 

 

 

1/4 OD

 

 

 

 

 

(OPTIONAL)

 

 

 

 

 

 

 

 

 

 

 

 

COLLECTOR BOX TO

 

 

 

 

11 2 (88mm)

 

 

 

TRAP RELIEF PORT

 

 

 

 

 

 

 

1/2 OD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDUCER HOUSING

 

 

 

(19mm)

3 4

 

 

 

DRAIN CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8 OD

 

 

 

 

 

 

 

 

 

COLLECTOR BOX

 

 

 

 

 

(181mm) 71 8

 

DRAIN CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

13 4 (44mm)

 

 

SCREW HOLE FOR

 

 

 

 

 

 

UPFLOW OR DOWN-

 

 

 

 

 

(3mm) 7 8

 

 

FLOW APPLICATIONS

 

 

 

 

WIRE TIE

 

 

(OPTIONAL)

 

 

 

 

 

 

21 4

 

 

 

 

 

 

 

GUIDES

 

 

1/2 IN. PVC OR CPVC

 

 

 

 

(WHEN USED)

 

(57mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT VIEW

 

SIDE VIEW

 

 

 

 

 

 

A07459

Fig. 6 - Condensate Trap

NOTE: Failure to use CPVC elbows may allow drain to kink, preventing draining.

k. Connect larger diameter drain tube and clamp (factory-supplied in loose parts bag) to condensate trap and clamp securely.

l.Route tube to coupling and cut to appropriate length.

m.Attach tube to coupling and clamp securely.

Condensate Trap (Alternate Upflow Orientation)

An alternate location for the condensate trap is the left-hand side of casing. (See Fig. 2 and 8.)

NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.

To relocate condensate trap to the left-hand side, perform the following:

1.Remove three tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.

4.Install condensate trap into left-hand casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

5.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

Condensate Trap Tubing (Alternate Upflow Orientation)

NOTE: See Fig. 8 or tube routing label on main furnace door to confirm location of these tubes.

8

Page 8
Image 8
Bryant 355CAV installation instructions Condensate Trap Alternate Upflow Orientation, Carbon Monoxide Poisoning Hazard