27
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP
(Master) Unused OFF OFF OFF ON OFF SelectBau d SelectBa ud
Modbus
(Slave) Unused OFF OFF ON ON OFF Select Baud Select Baud
N2
(Slave) Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE:
DS= Dip Switch
BACnetMS/TP SW3 example shown
Baud Rate Selections
BAUDRATE DS2 DS1
9600 OFF OFF
19,200 ON OFF
38,400 OFF ON
76,800 ON ON C07166
Fig. 52 --RTU--MP SW3 Dip Switch Settings
Local Access
BACview6Handheld
The BACview6is a keypad/display interface used to
connect to the RTU--MP to access the controlinformation,
read sensor values, and test the RTU, see Fig. 53. This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
BACview6to the RTU--MP’s J12 local access port.There
are 2 password protected levelsin the display (User and
Admin). The user password is defaulted to 0000 but can
be chan ged. The Adm in password i s1111 a nd cannot be
changed. There is a 10 minute auto logout if a screen is
idle. Contact your Bryant applications engineer for details
on navigation and screen content.
VirtualBACview
Virtual BACview is a freeware computer program that
functions as the BACview6Handheld. The USB Link
interface (USB--L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identical to the handheld.
RTU--MP TroubleshootingCommunication LEDs
The LEDs indicate if the controller is speaking to the
devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear.
C07170
Fig. 53 --BACview6Handheld Connect ions