Pad--mountedinstallation —
Prepare pad and unit supports
Check and tighten the bottom condensate drain
connectionplug
Rig and place unit
Convert unit to side duct connection arrangement
Install field--fabricatedductwork at unit duct openi ngs
Install outdoor air hood
Install condensate line trap and piping
Make electrical connections
Install otheraccessories
Frame--mountedinstallation —
Frame--mounted applications generally follow the
sequence for a curb installation. Adapt as required to
suit specificinstallation plan.
Step 3 — Inspectunit
Inspect unit for transportation damage. File any claim
with transportationagency.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data
plate agree with power supply provided.
Step 4 — ProvideUnit Support
RoofCurb Mount —
Accessory roof curb details and dimensions are shown in
Fig. 3. Assemble and install accessory roof curb in
accordance withinstructions shipped with the curb.
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are show in
Fig. 4. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork mustbe attachedto curband
not to the unit. The accessory thru--the--base power and
gas connection package must be installed before the unit
is set on the roofcurb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru--the--base service
connections to the basepan in accordance with the
accessoryinstallation instructions.
NOTE: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket suppliedwith
the roof curb as shown in Fig. 3. Improperly applied
gasket can also result in air leaks and poor unit
performance.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab thatextends a minimum of
6 in. (150 mm) beyond unit cabinet. Install a gravel apron
in front of condenser coil air inlet to prevent grass and
foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb
if required.
Alternate Unit Support (In Lieu of Curb or Slab
Mount) —
A non--combustible sleeper rail can be used in the unit
curb support area. If sleeper rails cannot be used, support
the long sides of the unit with a minimum of 3 equally
spaced 4--in. x 4--in. (102mm x 102 mm) pads on each
side.