NOTES:
1.Connect TRAN1 to H4 for 575V units.
2.Connect TRAN2 to black lead for 575V units.
3.Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and CB2. All others are 140%.
4.If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent.
5.Compressors and/or fan motors are thermally protected.