compressor 2 will turn on. If Y2 is deenergized at any time, only the last stage of compression that was energized will be turned off. If outdoor conditions are not suitable for econo- mizer cooling, the economizer will go to minimum position and cycle compressors 1 and 2 based on demand from Y1 and Y2 respectively. The compressors will be locked out when the SAT temperature is too low (less than 40 F for compressor 1 and less than 45 F for compressor 2.) After a compressor is locked out, it can restart after normal
The compressor time delay function maintains a minimum off time of 5 minutes, a minimum on time of 10 seconds, and a minimum delay before starting the second compressor of 10 seconds.
When heating, the heat stages respond to the demand from W1 and W2 of the thermostat input. Heating and cool- ing will be mutually
C. Cooling Capacity Control
The cooling capacity staging is shown in Table 6.
Table 6 Ð Cooling Capacity Staging Table,
Units with 2 Compressors
STAGES | 0 | 1 | 2 | 3 | |
ECONOMIZER | |||||
|
|
|
| ||
Compressor 1 | Off | Off | On | On | |
Compressor 2 | Off | Off | Off | On | |
|
|
|
|
|
NOTE: On units which require additional unloading, add suction pres- sure unloaders to compressor no. 1 only.
II.HEATING SECTION START-UP AND ADJUSTMENTS
CAUTION: Complete the required procedures given in the
Verify gas pressures before turning on heat as follows:
a.Turn off manual gas stop.
b.Connect pressure gage to supply gas tap (See Fig. 10 on page 8).
c.Connect pressure gage to manifold pressure tap on gas valve.
d.Supply gas pressure must not exceed 13.5 in. wg. Check pressure.
e.Turn on manual gas stop and set thermostat to HEAT position. After the unit has run for several minutes, verify that incoming pressure is 5.0 in. wg or greater, and that the manifold pressure is 3.5 in. wg. If mani- fold pressure must be adjusted, refer to Gas Valve Adjustment section on page 25.
A. Checking Heating Control Operation
Start and check the unit for proper heating control operation as follows:
1.Turn on manual gas stop.
2.Set thermostat setting to HEAT position.
3.The evaporator fan and
4.The evaporator fan and heaters will cycle off with no delay after thermostat temperature is satis®ed.
B.Gas Heating
The gas heat units incorporate two separate systems to pro- vide gas heat. Each system incorporates its own induced draft motor, Integrated Gas Control (IGC) board,
All of the gas heating control is performed through the IGC boards. The base module board serves only to initiate and terminate heating operation.
The base module board is powered by 24 vac. When the ther- mostat or room sensor calls for heating, power is sent from the base module board to W on each of the IGC boards. A
When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor as well as the ¯ame sensor. If the unit is controlled through a room thermostat set for fan auto., 45 seconds after ignition occurs, the
When additional heat is required, W2 closes and initiates power to the second stage of the main gas valves. When the ther- mostat is satis®ed, W1 and W2 open and the gas valves close interrupting the ¯ow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the
C. Power Exhaust Operation
The optional power exhaust packages are factory- or ®eld- installed with vertical units and optionally installed in the return air ductwork for horizontal applications. The stand- ard and the modulating power exhaust (used with non- modulatng to modulating conversion package) are the two packages offered. The modulating power exhaust package is equipped with a
Ð22Ð