V. FLUE HOOD
Flue hood is shipped inside gas section of unit. To install, se- cure ¯ue hood to access panel. See Fig. 7.
NOTE: When properly installed, ¯ue hood will line up with combustion fan housing. See Fig. 8.
Fig. 7 Ð Flue Hood Location
Fig. 8 Ð Combustion Fan Housing Location
VI. TRAP CONDENSATE DRAIN
See Fig. 2, 3, and 9 for drain location. Condensate drain is open to the atmosphere and must be trapped. Install a trapped drain at the drain location. One
Fig. 9 Ð Condensate Drain Connections
(Typical Roof Curb or
Slab Mount Shown)
Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air quality guidelines.
VII. GAS PIPING
Unit is equipped for use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a
WARNING: Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.
Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.
Size
Fig. 10 Ð Field Gas Piping
Ð8Ð