Bryant 580G manual V. Flue Hood, Ð Flue Hood Location, Ð Combustion Fan Housing Location

Models: 580G

1 44
Download 44 pages 8.75 Kb
Page 8
Image 8
V. FLUE HOOD

V. FLUE HOOD

Flue hood is shipped inside gas section of unit. To install, se- cure ¯ue hood to access panel. See Fig. 7.

NOTE: When properly installed, ¯ue hood will line up with combustion fan housing. See Fig. 8.

Fig. 7 Ð Flue Hood Location

Fig. 8 Ð Combustion Fan Housing Location

VI. TRAP CONDENSATE DRAIN

See Fig. 2, 3, and 9 for drain location. Condensate drain is open to the atmosphere and must be trapped. Install a trapped drain at the drain location. One 1-in. NPT coupling is pro- vided inside unit evaporator section for condensate drain con- nection. A trap at least 4-in. deep must be used. Trap must be installed to prevent freeze-up.

Fig. 9 Ð Condensate Drain Connections

(Typical Roof Curb or

Slab Mount Shown)

Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air quality guidelines.

VII. GAS PIPING

Unit is equipped for use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.

Install manual gas shutoff valve with a 1¤8-in. NPT pressure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 10.

Fig. 7 Ð Flue Hood LocationWARNING: Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.

Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Fig. 10 Ð Field Gas Piping

Ð8Ð

Page 8
Image 8
Bryant 580G manual V. Flue Hood, Ð Flue Hood Location, Ð Combustion Fan Housing Location, Vi. Trap Condensate Drain