Bryant 580G Ð Control Board LED Alarms, Ii. Error Code Summary, Ð IGC Board Error Code Summary

Models: 580G

1 44
Download 44 pages 8.75 Kb
Page 34
Image 34

Table 12 Ð Control Board LED Alarms

LED

 

ERROR

DESCRIPTION

TROUBLESHOOTING

BLINKS

 

CODE

COMMENTS

 

 

1

 

 

Normal Operation

The control board ¯ashes the red LED in one-second intervals

 

 

 

 

when the board is operating properly. Make sure DIP switch 3 is

 

 

 

 

closed.

2

 

HF-13

Compressor 1 Safety

The high or low pressure safety switch for compressor no. 1 has

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

no. 1 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 1 will be

 

 

 

 

locked out until the control board has been manually reset.

3

 

HF-14

Compressor 2 Safety

The high or low pressure safety switch for compressor no. 2 has

 

 

 

 

opened for 3 seconds. The error will be cleared and compressor

 

 

 

 

no. 2 will be allowed to turn on in 15 minutes. If the safeties have

 

 

 

 

been tripped 3 times in 90 minutes, compressor no. 2 will be

 

 

 

 

locked out until the control board has been manually reset.

4

 

HF-15

Thermostat Failure

The thermostat is calling for both heating and cooling at the same

 

 

 

 

time. The unit will operate on a ®rst call basis and will automati-

 

 

 

 

cally reset.

5

 

HF-05

SAT Thermistor Failure

The supply-air temperature (SAT) sensor has failed. First check for

 

 

 

 

wiring errors, then replace sensor.

6

 

HF-06

OAT Thermistor Failure

The outside-air temperature (OAT) sensor has failed. First check

 

 

 

 

for wiring errors, then replace sensor.

7

 

HF-03

DIP Switch 2 is Open

Close DIP switch 2.

8

 

HF-12

DIP Switch 1 is Open

Close DIP switch 1.

9

 

SE-05

Loss of Communications

Communications between the expansion board and the control

 

 

 

with Expansion Board

board have been interrupted. Ensure that an expansion board

 

 

 

 

is installed and wired using the wire harness supplied with the

 

 

 

 

expansion module. If an expansion board is not used, ensure that

 

 

 

 

DIP switch position 3 is in the closed position and reset power.

10

 

HF-16

Control Board Failure

Generated when hardware has failed on control board. Replace

 

 

 

 

the control board.

11

 

HF-17

Expansion Board Failure

Generated when hardware has failed on the expansion board.

 

 

 

 

Replace the expansion board.

LEGEND

 

 

 

DIP Ð Dual In-Line Package

 

 

LED Ð Light-Emitting Diode

 

 

II. ERROR CODE SUMMARY

A summary of the error codes is listed in Table 13. If more than one error code exists, they will be displayed on the LED of the IGC board in sequence. Fault history is deleted when power is turned off.

Table 13 Ð IGC Board Error Code Summary

INDICATION

ERROR MODE

ON

NORMAL OPERATION

OFF

HARDWARE FAILURE

1

FLASH

FAN ON/OFF DELAY MODIFIED

2

FLASHES

LIMIT SWITCH FAULT

3

FLASHES

FLAME SENSE FAULT

4

FLASHES

4 CONSECUTIVE LIMIT SWITCH FAULTS

5

FLASHES

IGNITION LOCKOUT FAULT

6

FLASHES

INDUCED DRAFT MOTOR FAULT

7

FLASHES

ROLLOUT SWITCH FAULT

8

FLASHES

INTERNAL CONTROL FAULT

 

 

 

III. INPUT AND OUTPUT CHANNEL DESIGNATIONS

Table 14 shows the input and output channel designations.

The Integrated Gas Controls for heating and cooling are shown in Fig. 45.

Ð34Ð

Page 34
Image 34
Bryant 580G manual Ð Control Board LED Alarms, Ii. Error Code Summary, Ð IGC Board Error Code Summary