NOTES:

1.Connect TRAN1 to H4 for 460 v units. Connect to H3 for 230 v. If 208/230 v units are run with a 208 v power supply connect to H2.

2.Connect TRAN2 to black lead for 460 v units. Connect to orange lead for 230 v units. If 208/230 v units are run with a 208 v power supply connect to red lead.

3.Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and CB2. All others are 140%.

4.If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.

5.Compressors and/or fan motors are thermally protected.

6.Three-phase motors are protected against primary single phasing conditions.

TABLE A

The Following Compressors Have Two

Parallel Wires Run From TB1 to the

Compressors

Compressor

Voltage

Wire

Model

Quantity

 

06D-537

208-230-3-60

2

TABLE B

The Following Fan Motors Have Two Parallel Wires Run From TB1 to the Fan Motors

Indoor

Voltage

Wire

Motor

Quantity

 

20 HP

208-230-3-60

2

 

 

 

Fig. 47 Ð Power Schematic; 580G,H240-360 Ð 208/230-3-60 and 460-3-60