NOTES:
1.Connect TRAN1 to H4 for 460 v units. Connect to H3 for 230 v. If 208/230 v units are run with a 208 v power supply connect to H2.
2.Connect TRAN2 to black lead for 460 v units. Connect to orange lead for 230 v units. If 208/230 v units are run with a 208 v power supply connect to red lead.
3.Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and CB2. All others are 140%.
4.If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
5.Compressors and/or fan motors are thermally protected.
6.
TABLE A
The Following Compressors Have Two
Parallel Wires Run From TB1 to the
Compressors
Compressor | Voltage | Wire | |
Model | Quantity | ||
| |||
2 |
TABLE B
The Following Fan Motors Have Two Parallel Wires Run From TB1 to the Fan Motors
Indoor | Voltage | Wire | |
Motor | Quantity | ||
| |||
20 HP | 2 | ||
|
|
|
Fig. 47 Ð Power Schematic;