Bryant 580G manual Xi. Accessories, A. Motormaster III Control Installation

Models: 580G

1 44
Download 44 pages 8.75 Kb
Page 19
Image 19
XI. ACCESSORIES

NOTES:

1.Unless otherwise speci®ed, all dimensions are to outside of part.

2.Dimensions are in inches.

Fig. 30 Ð Barometric Relief Damper and Power Exhaust Mounting Details

XI. ACCESSORIES

After all the factory-installed options have been adjusted, in- stall all ®eld-installed accessories. Refer to the accessory in- stallation instructions included with each accessory.

A. Motormaster III Control Installation

Install Field-Fabricated Wind Baffles

Wind baffles must be ®eld-fabricated for all units to ensure proper cooling cycle operation at low-ambient temperatures. See Fig. 31 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use ®eld- supplied screws to attach baffles to unit. Screws should be 1¤4-in. diameter and 5¤8-in. long. Holes for wind baffles are pre- punched in the unit sheet metal.

A. Motormaster III Control InstallationCAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only.

Fig. 31 Ð Motormaster III Baffle DetailsManual background 1 Manual background BOTH SIDES

18

77.7

0.312 DIA HOLES

61

17.167

 

BETWEEN

 

HOLES

 

(TYPICAL)

CROSS-BREAK

78.7

0.5

4.62

 

NOTE: All dimensions are in inches. Material: 20 gage galvanized steel or other non-corrosive material.

The wind baffles attach to ¯anges formed on the outer sheet metal of the unit where the condenser coil tube sheets attach.

Install Motormaster III Controls

Only one Motormaster III control is required per unit.

Motor Ð The circuit no. 1 (lead compressor) outdoor-fan motor (OFM) will need to be changed out in the ®eld to accommodate the Motormaster III accessory. The replace- ment motor part no. is HD52AK652.

The no. 1 compressor is located at the left side of the unit looking from the compressor end.

Sensor Ð Install the sensor for thermistor input control in the location shown in Fig. 32. Connect sensor leads to the violet and grey control signal leads on the Motormaster III control.

Signal Selection Switch Ð Remove the cover of the Motor- master III control. Set the switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).

Fig. 31 Ð Motormaster III Baffle Details

Motormaster III Control Ð The recommended mounting location is in the indoor fan section, mounted on the panel that separates the indoor and outdoor sections.

Electrical Connections

Manual backgroundWARNING: To avoid possibility of electrical shock and personal injury, turn off all power to unit before mak- ing electrical connections.

When replacing the OFM, reconnect the black, yellow, and blue wires from the outdoor fan contactor to the black, yel- low, and blue wires of the Motormaster III control. Run new wires from the red, orange, and brown wires to the leads of the new OFM. Connect the green wire from the control to ground.

NOTE: On all 575-v units, 2 transformers (part no. HT01AH851) must be used for each Motormaster III control to lower the supply voltage to the control to 460-v. Transform- ers can be mounted anywhere outside the control box.

Ð19Ð

Page 19
Image 19
Bryant 580G manual Xi. Accessories, A. Motormaster III Control Installation, Ð Motormaster III Baffle Details