NOTES:
1.Unless otherwise speci®ed, all dimensions are to outside of part.
2.Dimensions are in inches.
Fig. 30 Ð Barometric Relief Damper and Power Exhaust Mounting Details
XI. ACCESSORIES
After all the
A. Motormaster III Control Installation
Install
Wind baffles must be
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only.
1 BOTH SIDES
18
77.7
0.312 DIA HOLES
61
17.167 |
|
BETWEEN |
|
HOLES |
|
(TYPICAL) |
78.7 | 0.5 |
4.62 |
|
NOTE: All dimensions are in inches. Material: 20 gage galvanized steel or other
The wind baffles attach to ¯anges formed on the outer sheet metal of the unit where the condenser coil tube sheets attach.
Install Motormaster III Controls
Only one Motormaster III control is required per unit.
Motor Ð The circuit no. 1 (lead compressor)
The no. 1 compressor is located at the left side of the unit looking from the compressor end.
Sensor Ð Install the sensor for thermistor input control in the location shown in Fig. 32. Connect sensor leads to the violet and grey control signal leads on the Motormaster III control.
Signal Selection Switch Ð Remove the cover of the Motor- master III control. Set the switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).
Fig. 31 Ð Motormaster III Baffle Details
Motormaster III Control Ð The recommended mounting location is in the indoor fan section, mounted on the panel that separates the indoor and outdoor sections.
Electrical Connections
WARNING: To avoid possibility of electrical shock and personal injury, turn off all power to unit before mak- ing electrical connections.
When replacing the OFM, reconnect the black, yellow, and blue wires from the outdoor fan contactor to the black, yel- low, and blue wires of the Motormaster III control. Run new wires from the red, orange, and brown wires to the leads of the new OFM. Connect the green wire from the control to ground.
NOTE: On all
Ð19Ð