Bryant 580G manual Ð Field Control Thermostat Wiring, IX. OUTDOOR-AIRINLET ASSEMBLY A. Economizer

Models: 580G

1 44
Download 44 pages 8.75 Kb
Page 14
Image 14
Fig. 15 Ð Field Control Thermostat Wiring

Fig. 15 Ð Field Control Thermostat Wiring

IX. OUTDOOR-AIR INLET ASSEMBLY

A. Economizer

NOTE: If accessory power exhaust or barometric relief pack- ages are being added to the unit, install power exhaust or barometric relief before installing economizer hoods.

Economizer Hood Assembly

The economizer hood is shipped in a package secured to the outside of the unit and must be ®eld assembled. There are 2 hoods on every unit. The 580H units are side supply and side return. The return duct limits access to economizer ®lters from below. Filter tracks (mounting angle without tabs) must be installed correctly to allow access to economizer ®lters from each side.

NOTE: Before assembly of the economizer hood, check along the outer edges of the economizer assembly for any seal strip protruding past the ¯anges. Trim the excess seal strip so that it is ¯ush with the economizer assembly ¯anges.

Perform the following procedure to assemble the economizer hood:

1.a. Apply black seal strip (provided in package) to out- side top edge of hood sides. Wrap seal strip over to cover top ¯ange (4 hood sides). Make certain seal strip covers screw holes. Allow strip to overhang 1¤8 in. past end opposite mounting ¯ange. See Fig. 16.

b.Assemble hood sides, top, and cross member with gas- keted screws provided. See Fig. 17.

c.Attach 10 green speed clips (provided) to hood top.

d.Apply black seal strip to mounting ¯anges (cover holes) of hood sides. See Fig. 18.

NOTE: Each hood assembly has a slotted side that should be adjacent to the other hood when mounted to the unit.

e.Apply black seal strip to hood top mounting ¯ange. Seal strip of hood top mounting ¯ange must press against seal strip of hood side mounting ¯anges. See Fig. 19.

f.Add gray foam strip (provided) to cross members at bottom tray. See Fig. 20.

TOP

FLANGE

BLACK

SEALHOOD SIDE STRIP

Fig. 16 Ð Adding Seal Strip to Top of Hood Sides

NOTE: Left side economizer hood has mounting angle without tabs and ®lter track assembled end on opposite side.

Fig. 17 Ð Economizer Hood Assembly

(Right-Side Economizer Hood Shown)

Exhaust Mounting Details

g.Place gray foam strip on inside of slotted hood side between ®lter and cross member opposite mounting end. See Fig. 21.

h.Attach gray foam strip to blockoff baffle on outer face area of ¯ange. See Fig. 22.

2.Remove the screws on each end and along top of damper assembly of unit. Remove top 2 screws on each side of ®lter panel under damper assembly. Set hood assembly in place and attach to unit using these screws.

3.Attach accessory enthalpy bracket on hood side fur- thest from control box end. Locate bracket on inside upper right hand corner using hood mounting holes. Mount outdoor-air thermistor to enthalpy bracket (if pur- chased). Attach and wire enthalpy assembly. Place quick connects on enthalpy wires.

Ð14Ð