Install a solenoid valve (field supplied) in liquid line directly before expansion valve. Solenoid valve is necessary for single pumpout control used on 06D, 07D units. Refrigerant filter drier and moisture indicator are shipped with 07D condensing units for field installation. Install in liquid line according to manufacturer’s instructions.

Relief valve located on top of condenser (07D units) will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from safety device to outdoors.

Refer to Carrier System Design Manual, Part 3, for standard piping techniques.

COMPRESSOR UNITS — Connect high- and low-pressure switch capillary tubes from control box to compressor. See Fig. 2.

Install discharge line muffler (accessory) in discharge line as close to compressor shutoff valve as possible.

Electrical Connections

UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the % voltage imbalance:

% Voltage Imbalance =

max voltage deviation from average voltage

100 x

average voltage

Example: Supply voltage is 230-3-60

AB = 236 volts

BC = 229 volts

AC = 234 volts

Average Voltage =

236 + 229 + 234

= 233 volts

3

 

 

Determine maximum deviation from average voltage:

(AB) 236 – 233 = 3 volts (BC) 233 – 229 = 4 volts (AC) 234 – 233 = 1 volt

Maximum deviation is 4 volts. Determine % voltage imbalance:

% Voltage Imbalance =100 x 2334 = 1.7%

This amount of phase imbalance is satisfactory as it is below the maximum allowable of 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

ELECTRICAL DATA NOTES

1.All 06D and 07D units are across-the-line start.

2.Wire sizes are based on TW type copper wire. Maximum wire lengths based on data from Table 1 will result in a 1% voltage drop to compressor. Where up to 3% voltage drop is allowed, the run length can be increased to 3 times the length calculated from data in Table 1.

3.The 06D compressor unit electrical data shown in Table 1 does not apply for 06D compressors used as an integral part of other Carrier equipment. See proper installation book for electrical information.

WIRING — Power supply must correspond with unit name- plate electrical characteristics (units are internally wired at factory for nameplate voltage). Field wiring must comply with local and national codes.

Install a branch circuit fused disconnect of adequate size to handle starting current.

LINE POWER — Connect line power to the compressor con- tactor C. For example, connect L1 to terminal 11, L2 to termi- nal 12 and L3 to terminal 13. See Fig. 3.

Table 1 — Compressor Electrical Data

COMPRESSOR

VOLTAGE

 

 

 

 

MOTOR WINDING

PART NUMBER

HP

MCC

RLA

LRA

RESISTANCE

(3 Ph-60 Hz)

06D*

 

 

 

 

(Ohms)

 

 

 

 

 

 

808

575

 

7

5

28.4

5.0

 

208/230

3

17.4

12.4

71

0.78

M

 

460

 

8.7

6.2

35.5

3.1

313

575

 

10.8

7.7

40

3.3

 

 

 

208/230

5

27

19.3

100

0.5

 

 

460

 

13.5

9.6

50

2.1

 

818

575

 

17.6

12.6

64

2.6

 

208/230

6.5

44

31.4

160

0.42

 

 

460

 

22

15.7

80

1.7

 

825

575

 

22.2

15.9

79

2.0

 

208/230

7.5

55.5

39.6

198

0.31

A

 

460

 

27.8

19.8

99

1.3

328

575

 

25

17.9

91

1.7

 

 

 

208/230

10

62

44.3

228

0.26

 

 

460

 

31

22.1

114

1.0

 

537

575

 

32

22.9

96

1.2

 

208/230

15

89

63.6

266

0.18

 

 

460

 

40

28.6

120

0.72

LEGEND

LRA — Locked Rotor Amps

MCC — Maximum Continuous Current

RLA — Rated Load Amps

*Refer to physical data table to match compressor with correct com- pressor unit or water-cooled condensing unit.

NOTES:

1.RLA (rated load amps) value shown is: MCC 1.40 = RLA.

2.For minimum contactor sizing, use RLA value determined by: MCC 1.40 = RLA.

3.For wiring sizing, the RLA value can be determined by: MCC 1.56 = RLA.

4.Compressor operating amps at any specific conditions can only be determined from a performance curve.

5.RLA values for 06D compressor protected by a calibrated circuit breaker will depend on must-trip value of circuit breaker.

6.Ohm values shown for resistance are approximate and shown for reference only. Motors from different vendors and motors of different efficiencies can differ up to 15% from data shown.

7.Electrical data for compressor part numbers 06DR and 50 Hz models (not shown) are available from Carrier Sales Representative.

4

Page 4
Image 4
Carrier 06D specifications Electrical Connections