Carrier 06D specifications Troubleshooting, Compressor cycles on low-pressure

Models: 06D

1 20
Download 20 pages 37.93 Kb
Page 18
Image 18
TROUBLESHOOTING

TROUBLESHOOTING

Read Safety Considerations on page 1 before proceeding with troubleshooting.

PROBLEM

CAUSE

REMEDY

Compressor does not run.

Main power line open.

Replace fuse or reset circuit breaker.

 

Safety thermostat tripped.

Reset thermostat.

 

Condenser water pump not running — power off.

Restart.

 

Pump binding.

Free pump.

 

Incorrect wiring.

Rewire.

 

Motor burned out.

Replace.

 

Control stuck open.

Replace control.

 

Loose terminal connection.

Check connections.

 

Improperly wired controls.

Check wiring and rewire.

 

Low line voltage.

Check line voltage — determine location of

 

 

voltage drop.

 

Compressor motor defective.

Check motor winding for open or short.

 

 

Replace compressor if necessary.

 

Seized compressor.

Replace compressor.

Compressor cycles on low-pressure

Low-pressure control erratic in action.

Raise differential setting, check capillary for

control.

 

pinches, replace control.

 

Suction shutoff valve partially closed.

Open valve.

 

Low refrigerant charge.

Add refrigerant.

 

Plugged suction strainer.

Clean strainer.

 

Defective TXV.

Replace.

Compressor cycles on high-pressure

High-pressure control erratic in action.

Check capillary tube for pinches. Set control as

control.

 

required.

 

Discharge valve partially closed.

Open valve.

 

Air in system.

Purge.

 

Condenser scaled (or airflow restricted).

Clean condenser.

 

Receiver not properly vented, refrigerant backs

Repipe as required.

 

up into evap condenser.

 

 

Condenser water pump or fans not

Start pump or fans.

 

operating.

 

 

Refrigerant overcharge.

Purge.

Insufficient capacity.

Low refrigerant charge.

Add refrigerant.

 

Control set too high.

Reset control.

 

Expansion valve plugged.

Clean or replace.

 

Inefficient compressor.

Check valves and pistons.

 

Expansion valve setting too high.

Lower setting.

 

Iced or dirty evaporator.

Defrost or clean.

 

Evaporator too small.

Add surface or replace.

 

Condensing unit too small.

Add unit or replace.

 

Expansion valve too small.

Raise suction pressure with larger valve.

 

Restricted or small gas lines.

Clear restriction or increase line size.

Unit operates long or continuously.

Low refrigerant charge.

Add refrigerant.

 

Control contacts fused.

Replace control.

 

Air in system.

Purge.

 

Partially plugged or plugged expansion valve or

Clean or replace.

 

strainer.

 

 

Defective insulation.

Replace or repair.

 

Service load.

Keep doors and windows closed.

 

Inefficient compressor.

Check valves.

 

Condenser scaled.

Clean condenser.

 

Restricted evaporator air.

Defrost coil, clean filters and ductwork.

LEGEND

 

 

TXV — Thermostatic Expansion Valve

 

 

18

Page 18
Image 18
Carrier 06D specifications Troubleshooting, Compressor cycles on low-pressure, Compressor cycles on high-pressure