Table 14 Ð Individual Component Ratings

POWER SOURCE

ITEM

AVERAGE kW

DESIGN CENTER

SUPPLY

FLA

LRA

VOLTAGE

V-PH-HZ

 

 

 

 

 

 

Seal Leakage

0.23

115

115-1-50/60

4.78

21.7

1*

Pump

 

 

 

 

 

(17EX Only)

Motor Space

0.50

115

115-1-50/60

4.35

4.35

 

Heater

 

 

 

 

 

 

 

Control Module

0.40

115

115-1-60

3.50

Ð

 

and Actuator

115-1-50

 

 

 

 

Oil Sump Heater

1.00

115

115-1-60

8.70

Ð

 

 

115-1-50

 

 

 

 

 

 

 

 

1.35

220

200/240-3-60

4.32

24.5

 

 

1.30

430

380/480-3-60

2.15

12.2

Oil Pump

1.37

563

507/619-3-60

2.13

25.0

 

 

1.49

230

220/240-3-50

4.83

28.0

 

 

1.49

393

346/440-3-50

2.59

12.2

1**

Hot Gas

0.20

115

115-1-50/60

2.00

4.75

Bypass

 

 

 

 

 

 

 

 

 

204

200/208-3-60

10.90

63.5

3**

Pumpout

 

230

220/240-3-60

9.50

57.5

3.41

460

440/480-3-60

4.70

28.8

(Optional)

Compressor

 

575

550/600-3-60

3.80

23.0

 

 

 

 

 

 

400

380/415-3-50

4.70

28.8

LEGEND

FLA Ð Full Load Amps LRA Ð Locked Rotor Amps

*Available for 17EX machines only. ²Available for 17/19EX machines.

**Available as an option on 17/19EX machines.

NOTE: The oil pump is powered through a ®eld wiring terminal into the power panel. Power to the controls and oil heater via the power panel must be on circuits that can provide continuous service when the compressor starter is disconnected.

22

Page 22
Image 22
Carrier 19EX, 17 installation instructions Individual Component Ratings, Ph-Hz