IMPORTANT: Wiring shown is typical and not intended to show detail |
| 3.3 | Pilot relays can control cooler and condenser pump and tower fan motor contactor | |||
|
| coil loads rated 10 amps at 115 vac up to 3 amps at 600 vac. Control wiring required | ||||
for a speci®c installation. Refer to certi®ed ®eld wiring diagrams for |
|
| for Carrier to start pumps and tower fan motors must be provided to assure machine | |||
additional information. Certi®ed drawings are available upon request. |
|
| protection. If primary pump and tower fan motor control is by other means, also | |||
|
|
|
|
| provide a parallel means for control by Carrier. Do not use starter control trans- | |
| LEGEND |
|
|
| former as the power source for pilot relay loads. | |
|
|
| 3.4 | Do not route control wiring carrying 30 v or less within a conduit which has wires | ||
| Required Power Wiring | Options Wiring | ||||
|
| carrying 50 v or higher or along side wires carrying 50 v or higher. | ||||
| Required Control Wiring |
|
|
| ||
|
|
| 3.5 | Voltage selector switch in machine power panel is factory set for 115 v control power | ||
NOTES: |
|
| ||||
|
|
| source. When 230 v control power source is used, set switch to 230 v | |||
I. GENERAL |
|
|
| position. | ||
1.0 | Starters shall be designed and manufactured in accordance with Carrier Engineer- | 3.6 | Control wiring cables between starter and power panel must be shielded with mini- | |||
| ing Requirement |
|
|
| mum rating of 600 v, 80 C. Ground shield at starter. | |
1.1 | All | 3.7 | Voltage to terminals LL1 and LL2 comes from a control transformer in a starter built | |||
| conductors and devices, must be in compliance with all applicable codes and job |
| to Carrier speci®cations. Do not connect an outside source of control power to the | |||
| speci®cations. |
|
|
| compressor motor starter (terminals LL1 and LL2). An outside power source will | |
1.2 | The routing of |
| produce dangerous voltage at the line side of the starter, because supplying voltage | |||
| installed devices, must not interfere with equipment access or the reading, adjust- |
| at the transformer secondary terminals produces input level voltage at the trans- | |||
| ing, or servicing of any component. |
|
|
| former primary terminals. | |
1.3 | Equipment, installation, and all starting and control devices must comply with de- | IV. POWER WIRING BETWEEN STARTER AND COMPRESSOR MOTOR | ||||
| tails in equipment submittal drawings and literature. | 4.0 | Low voltage (600 v or less) compressor motors have (6) 1¤2 in. terminal studs (lead | |||
1.4 Contacts and switches are shown in the position they would assume with the circuit |
| connectors not supplied by Carrier). Either 3 or 6 leads must be run between com- | ||||
| deenergized and the chiller shut down. |
|
|
| pressor motor and starter, depending on type of motor starter employed. If only 3 | |
1.5 | WARNING Ð Do not use aluminum conductors. |
|
|
| leads are required, jumper motor terminals as follows: 1 to 6, 2 to 4, 3 to 5. Center | |
1.6 | Installer is responsible for any damage caused by improper wiring between starter |
| to center distance between terminals is 2.73 inches. Compressor motor starter must | |||
| have nameplate stamped as to conforming with Carrier requirement | |||||
| and machine. |
|
|
| ||
|
|
| 4.1 | When more than one conduit is used to run conductors from starter to compressor | ||
II. POWER WIRING TO STARTER |
|
| ||||
|
|
| motor terminal box, one conductor from each phase must be in each conduit, to | |||
2.0 | Power conductor rating must meet minimum unit nameplate voltage and compres- |
| prevent excessive heating. (e.g., conductors to motor terminals 1, 2 and 3 in one | |||
| sor motor RLA (rated load amps). |
|
|
| conduit, and these to 4, 5 and 6 in another.) | |
| When (3) conductors are used: |
|
| 4.2 | Compressor motor power connections can be made through top, bottom, or right | |
| Minimum ampacity per conductor = 1.25 x compressor RLA |
| side of compressor motor terminal box by rotating the terminal box and using holes | |||
| When (6) conductors are used: |
|
|
| cut by contractor to suit conduit. Flexible conduit should be used for the last few feet | |
| Minimum ampacity per conductor = 0.721 x compressor RLA |
| to the terminal box for unit vibration isolation. Use of stress cones or 12 conductors | |||
2.1 | Lug adapters may be required if installation conditions dictate that conductors be |
| larger than 500 MCM may require an oversize (special) motor terminal box (not | |||
| supplied by Carrier). Lead connections between | |||||
| sized beyond the minimum ampacity required. Contact starter supplier for lug |
| ||||
|
| starters must not be insulated until Carrier personnel have checked compressor | ||||
| information. |
|
|
| ||
|
|
|
| rotation. | ||
2.2 Compressor motor and controls must be grounded by using equipment grounding |
| |||||
4.3 | Compressor motor frame to be grounded in accordance with the National Electrical | |||||
| lugs provided inside starter enclosure. |
|
| |||
|
|
|
| Code | ||
|
|
|
|
| ||
III. CONTROL WIRING |
|
|
| (2) Thomas and Betts pressure connectors for 350 to 800 MCM wire, supplied and | ||
3.0 | Field supplied control conductors to be at least 18 AWG (American Wire Gage) or |
| located in the back upper and lower right side corners of the compressor motor | |||
| terminal box. | |||||
| larger. |
|
|
| ||
|
|
| 4.4 | Do not allow motor terminals to support weight of wire cables. Use cable supports | ||
3.1 | Chilled water and condenser water ¯ow switch contacts, optional remote start | |||||
| and strain reliefs as required. | |||||
| device contacts and optional spare safety device contacts, must have 24 vdc rating. |
| ||||
| 4.5 | Use back up wrench when tightening lead connectors to motor terminal studs. Torque | ||||
| Max current is 60 ma, nominal current is 10 ma. Switches with gold plated | |||||
| biurcated contacts are recommended. |
|
|
| to |
3.2Remove jumper wire between 12A and 12B before connecting auxiliary safeties be- tween these terminals.
→Fig. 35 Ð 23XL Typical Field Wiring with
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.
Book | 2 |
| PC 211 | Catalog No. | Printed in U.S.A. | Form | Pg 34 | 796 | Replaces: | |
Tab | 5e |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|