Fig. 15 Ð Standard Isolation

VIEW B-B

NOTES:

1. Dimensions in ( ) are in millimeters.

2. Isolation package includes 4 shear ¯ex pads.

Fig. 15 Ð Standard Isolation

HRS Ð Hot Rolled Steel

NOTES:

1. Dimensions in ( ) are in millimeters.

2.Accessory (Carrier supplied, ®eld installed) soleplate package in- cludes 4 soleplates, 16 jacking screws and leveling pads. Re- quires accessory spring vibration isolation package.

3.Jacking screws to be removed after grout has set.

4.Thickness of grout will vary, depending on the amount necessary to level chiller. Use only pre-mixed non-shrinking grout, Celcote HT-648 or Master Builders 636, 0 -11¤2(38.1) to 0 -21¤4(57) thick.

Fig. 16 Ð Accessory Isolation

NOTE: The accessory spring vibration isolation package is supplied by Carrier for installation in the ®eld.

Fig 17 Ð 23XL Accessory Spring Vibration Isolation (Shown With Accessory Soleplates)