Carrier 30XW325-400 manual Electrical data, Standard Single Input Power Configuration

Models: 30XW325-400

1 32
Download 32 pages 43.36 Kb
Page 26
Image 26
Electrical data

Electrical data

STANDARD SINGLE INPUT POWER CONFIGURATION

30XW

UNIT VOLTAGE

 

NO. POWER

 

 

 

ICF

REC FUSE

CONTROL CIRCUIT

UNIT

 

Supplied

SUPPLY

MCA

MOCP

 

 

MCA and

V-Ph-Hz

 

 

 

SIZE

V-Ph-Hz

SIZE

 

 

 

CONDUCTORS

 

 

 

 

 

MOCP

Min

 

Max

 

 

WD

 

XL

 

 

 

 

 

 

 

 

200-3-60

187

 

220

9

920.3

1200

1347.0

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

799.0

1000

1171.1

 

1000

115-1-60

20

325

380-3-60

342

 

418

6

487.6

700

710.7

 

1753.7

600

115-1-60

20

 

460-3-60

414

 

506

6

401.0

500

586.2

 

1448.2

450

115-1-60

20

 

575-3-60

518

 

633

3

317.3

450

467.0

 

1157.0

400

115-1-60

20

 

200-3-60

187

 

220

12

1168.2

1600

1848.2

 

1600

115-1-60

20

325

230-3-60

207

 

253

9

1018.4

1200

1608.6

 

1200

115-1-60

20

380-3-60

342

 

418

6

614.5

800

973.1

 

2452.1

700

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

510.8

700

805.0

 

2027.0

600

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

406.8

500

642.8

 

1620.8

450

115-1-60

20

 

200-3-60

187

 

220

9

920.3

1200

1347.0

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

799.0

1000

1171.1

 

1000

115-1-60

20

350

380-3-60

342

 

418

6

487.6

700

710.7

 

1753.7

600

115-1-60

20

 

460-3-60

414

 

506

6

401.0

500

586.2

 

1448.2

450

115-1-60

20

 

575-3-60

518

 

633

3

317.3

450

467.0

 

1157.0

400

115-1-60

20

 

200-3-60

187

 

220

12

1168.2

1600

1848.2

 

1600

115-1-60

20

350

230-3-60

207

 

253

9

1018.4

1200

1608.6

 

1200

115-1-60

20

380-3-60

342

 

418

6

614.5

800

973.1

 

2452.1

700

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

510.8

700

805.0

 

2027.0

600

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

406.8

500

642.8

 

1610.8

450

115-1-60

20

 

200-3-60

187

 

220

9

1041.3

1200

1400.8

 

1200

115-1-60

20

 

230-3-60

207

 

253

9

902.9

1200

1217.3

 

1200

115-1-60

20

400

380-3-60

342

 

418

6

545.2

700

736.3

 

1779.3

700

115-1-60

20

 

460-3-60

414

 

506

6

452.9

600

609.3

 

1471.3

600

115-1-60

20

 

575-3-60

518

 

633

3

366.3

500

488.8

 

1178.6

450

115-1-60

20

 

200-3-60

187

 

220

12

1329.8

1600

1920.0

 

1600

115-1-60

20

400

230-3-60

207

 

253

12

1156.7

1600

1670.1

 

1600

115-1-60

20

380-3-60

342

 

418

6

700.9

1000

1011.5

 

2490.5

800

115-1-60

20

HM

 

 

460-3-60

414

 

506

6

579.8

800

835.7

 

2057.7

700

115-1-60

20

 

 

 

 

575-3-60

518

 

633

6

464.4

600

668.4

 

1646.4

600

115-1-60

20

 

 

LEGEND

ICF

Maximum Instantaneous Current Flow

HM

Heat Machine Units

LRA

Locked Rotor Amps

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP —

Maximum Overcurrent Protection

RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

NOTES:

1.Each main power source must be supplied from a field-supplied fused electrical service with a (factory-installed or field-installed) disconnect located in sight from the unit.

2.Control circuit power must be supplied from a separate source through a field-supplied disconnect. An optional control transformer may be used to provide control circuit power from the main unit power supply.

3.Maximum instantaneous current flow (ICF) during start-up is the point in the starting sequence where the sum of the LRA for the start-up compressor, plus the total RLA for all running compressors is at a maximum.

4.Maximum incoming wire size for each terminal block is 500 kcmil.

5.Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.

6.Use copper conductors only.

7.The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows: RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up from the result. The RLAs are listed on the nameplate.

26

Page 26
Image 26
Carrier 30XW325-400 manual Electrical data, Standard Single Input Power Configuration