Guide specifications
Water-Cooled Chiller
HVAC Guide Specifications
Size Range: 325 to 400 Nominal Tons (1133 to 1354 kW)
Carrier Model Number: 30XW
Part 1 — General
1.01 SYSTEM DESCRIPTION
Microprocessor controlled
1.02QUALITY ASSURANCE
A.Unit shall be rated in accordance with AHRI Stan- dard 550/590 (U.S.A.), latest edition.
B.Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).
C.Unit shall be manufactured in a facility registered to ISO 9001:2000 Manufacturing Quality Standard.
D.
1.03DELIVERY, STORAGE, AND HANDLING
A.Unit controls shall be capable of withstanding 150 F (65.5 C) storage temperatures in the control compartment.
B.Chiller and starter should be stored indoors, pro- tected from construction dirt and moisture. An inspection should be conducted under shipping tarps, bags, or crates to be sure water has not col- lected during transit. Protective shipping covers should be kept in place until machine is ready for installation. The inside of the protective cover should meet the following criteria:
1.Temperature is between 40 F (4.4 C) and 120 F (48.9 C).
2.Relative humidity is between 10% and 80%
Part 2 — Products
2.01EQUIPMENT
A.General:
Factory assembled,
B.Compressors:
1.
2.Each compressor shall be equipped with a dis- charge shutoff valve.
C.Evaporator:
1.Shall be tested and stamped in accordance with ASME Code (U.S.A.) for a refrigerant
2.Shall be mechanically cleanable
3.Tubes shall be internally enhanced, seamless- copper type, and shall be rolled into tube sheets.
4.Shall be equipped with victaulic fluid connections.
5.Shell shall be insulated with
6.Shall have a evaporator drain and vent.
7.Design shall incorporate 2 independent refrig- erant circuits.
8.Shall include isolation valves to allow isolation of the refrigerant charge in either the evapora- tor or the condenser.
9.Shall be equipped with
D.Condenser:
1.Shall be tested and stamped in accordance with ASME code (U.S.A.) for a refrigerant
2.Shall be mechanically cleanable
3.Tubes shall be internally enhanced, seamless- copper type, and shall be rolled into tube sheets.
4.Shall be equipped with victaulic water connections.
5.Design shall incorporate 2 independent refrig- erant circuits.
E.Heat Machines:
1.Condenser shall be tested and stamped in accordance with ASME Code (U.S.A.) for a refrigerant
2.Design shall incorporate 2 independent refrig- erant circuits.
3.Heat machine condensers shall include factory- installed thermal insulation on the condenser, condenser flow switch and leaving water temperature sensor. Heat machine units require
29