Carrier 30XW325-400 manual Optional Dual Input Power Configuration, Supply

Models: 30XW325-400

1 32
Download 32 pages 43.36 Kb
Page 27
Image 27

OPTIONAL DUAL INPUT POWER CONFIGURATION

30XA

UNIT VOLTAGE

 

NO. POWER

 

 

ICF

REC FUSE

CONTROL CIRCUIT

UNIT

 

Supplied

SUPPLY

MCA

MOCP

 

MCA and

V-Ph-Hz

 

 

SIZE

V-Ph-Hz

SIZE

 

 

 

CONDUCTORS

 

 

 

 

 

Min

 

Max

 

 

WD

XL

 

 

 

MOCP

 

200-3-60

187

 

220

6/6

511.3/511.3

800/800

938/938

700

700

115-1-60

20

 

230-3-60

207

 

253

6/6

443.9/443.9

700/700

816/816

600

600

115-1-60

20

325

380-3-60

342

 

418

3/3

270.9/270.9

450/450

494/494

1537/1537

350

350

115-1-60

20

 

460-3-60

414

 

506

3/3

222.8/222.8

400/400

408/408

1270/1270

300

300

115-1-60

20

 

575-3-60

518

 

633

3/3

176.3/176.3

300/300

326/326

1016/1016

225

225

115-1-60

20

 

200-3-60

187

 

220

6/6

649.0/649.0

1000/1000

1329/1329

800

800

115-1-60

20

325

230-3-60

207

 

253

6/6

565.8/565.8

1000/1000

1156/1156

700

700

115-1-60

20

380-3-60

342

 

418

3/3

341.4/341.4

600/600

700/700

2179/2179

450

450

115-1-60

20

HM

 

460-3-60

414

 

506

3/3

283.8/283.8

500/500

578/578

1800/1800

350

350

115-1-60

20

 

 

 

575-3-60

518

 

633

3/3

226.0/226.0

400/400

462/462

1440/1440

300

300

115-1-60

20

 

200-3-60

187

 

220

6/6

511.3/511.3

800/800

938/938

700

700

115-1-60

20

 

230-3-60

207

 

253

6/6

443.9/443.9

700/700

816/816

600

600

115-1-60

20

350

380-3-60

342

 

418

3/3

270.9/270.9

450/450

494/494

1537/1537

350

350

115-1-60

20

 

460-3-60

414

 

506

3/3

222.8/222.8

400/400

408/408

1270/1270

300

300

115-1-60

20

 

575-3-60

518

 

633

3/3

176.3/176.3

300/300

326/326

1016/1016

225

225

115-1-60

20

 

200-3-60

187

 

220

6/6

649.0/649.0

1000/1000

1329/1329

800

800

115-1-60

20

350

230-3-60

207

 

253

6/6

565.8/565.8

1000/1000

1156/1156

700

700

115-1-60

20

380-3-60

342

 

418

3/3

341.4/341.4

600/600

700/700

2179/2179

450

450

115-1-60

20

HM

 

460-3-60

414

 

506

3/3

283.8/283.8

500/500

578/578

1800/1800

350

350

115-1-60

20

 

 

 

575-3-60

518

 

633

3/3

226.0/226.0

400/400

462/462

1440/1440

300

300

115-1-60

20

 

200-3-60

187

 

220

6/6

578.5/578.5

1000/1000

938/938

700

700

115-1-60

20

 

230-3-60

207

 

253

6/6

501.6/501.6

800/800

816/816

700

700

115-1-60

20

400

380-3-60

342

 

418

3/3

302.9/302.9

500/500

494/494

1537/1537

400

400

115-1-60

20

 

460-3-60

414

 

506

3/3

251.6/251.6

450/450

408/408

1270/1270

350

350

115-1-60

20

 

575-3-60

518

 

633

3/3

203.5/203.5

350/350

326/326

1016/1016

250

250

115-1-60

20

 

200-3-60

187

 

220

6/6

738.8/738.8

1200/1200

1329/1329

1000

1000

115-1-60

20

400

230-3-60

207

 

253

6/6

642.6/642.6

1000/1000

1156/1156

800

800

115-1-60

20

380-3-60

342

 

418

6/6

389.4/389.4

600/600

700/700

2179/2179

500

500

115-1-60

20

HM

 

460-3-60

414

 

506

3/3

322.1/322.1

500/500

578/578

1800/1800

400

400

115-1-60

20

 

 

 

575-3-60

518

 

633

3/3

258.0/258.0

450/450

462/462

1440/1440

350

350

115-1-60

20

 

 

LEGEND

ICF

Maximum Instantaneous Current Flow

HM

Heat Machine Units

LRA

Locked Rotor Amps

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP —

Maximum Overcurrent Protection

RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

NOTES:

1.Each main power source must be supplied from a field-supplied fused electrical service with a (factory-installed or field-installed) disconnect located in sight from the unit.

2.Control circuit power must be supplied from a separate source through a field-supplied disconnect. An optional control transformer may be used to provide control circuit power from the main unit power supply.

3.Maximum instantaneous current flow (ICF) during start-up is the point in the starting sequence where the sum of the LRA for the start-up com- pressor, plus the total RLA for all running compressors is at a maximum.

4.Maximum incoming wire size for each terminal block is 500 kcmil.

5.Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.

6.Use copper conductors only.

7.The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse one size down from the result. The RLAs are listed on the nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:

RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one size up from the result. The RLAs are listed on the nameplate.

27

Page 27
Image 27
Carrier 30XW325-400 manual Optional Dual Input Power Configuration, NO. Power ICF REC Fuse Control Circuit Unit, Supply