Carrier 30XW325-400 manual Dimensions, a30-4745, 30XW UNIT DIMENSIONS, Suction End, Discharge End

Models: 30XW325-400

1 32
Download 32 pages 43.36 Kb
Page 12
Image 12
Dimensions

Dimensions

30XW UNIT DIMENSIONS

a30-4745

SEE NIH EVAPORATOR

DETAIL FOR NOZZLE

MEASUREMENTS

SUCTION

END

SEE NIH CONDENSER

DETAIL FOR NOZZLE

MEASUREMENTS

EVAPORATOR

CONDENSER

MLV (OPTIONAL)

MLV (OPTIONAL)

DISCHARGE END

STANDARD 30XW UNIT DIMENSIONS

30XW UNIT

OPERATING

MOUNTING LOCATION WEIGHT, lb [kg]

 

DIMENSIONS (ft-in. [mm])

SIZE

WEIGHT, lb [kg]

1

2

3

4

 

A

 

B

 

C

325

14,319 [6495]

3734 [1694]

3828 [1736]

3337 [1514]

3420 [1551]

6-3/8

[1837]

6-3/8

[1837]

3/8

[9.53]

350

14,515 [6584]

3785 [1717]

3880 [1760]

3383 [1535]

3467 [1573]

6-3/8

[1837]

6-3/8

[1837]

3/8

[9.53]

400

14,759 [6695]

3848 [1745]

3946 [1790]

3439 [1560]

3526 [1599]

6-3/8

[1837]

6-3/8

[1837]

3/8

[9.53]

NOTES:

1.Weights shown for standard chiller (2 pass with NIH, victaulic waterboxes).

2.See page 14 for unit mounting locations.

30XW UNIT AND WATERBOX DIMENSIONS

LEGEND

MLV — Minimum Load Valve

MWB — Marine Waterbox

NIH — Nozzle-In-Head

SSV — Suction Service Valve

CONNECTIONS

PASSES

WATERBOX

NOZZLE

D

E

F

 

MAX UNIT OPERATING WEIGHT lb [kg]

 

 

(EVAP/COND)

TYPE

ft-in. [mm]

ft-in. [mm]

ft-in. [mm]

325

350

400

 

 

NIH/NIH

Victaulic

13-33/4[4057]

 

 

 

14,319 [6495]

14,515 [6495]

14,759 [6695]

 

 

Flange

13-91/16[4193]

 

 

 

14,651 [6646]

14,847 [6646]

15,091 [6845]

 

 

 

 

 

 

 

 

NIH/MWB

Victaulic

 

 

 

 

14,498 [6576]

14,694 [6576]

14,938 [6776]

Same Ends

 

Flange

 

3-113/8[1210]

6-611/16

[1999]

14,739 [6685]

14,935 [6685]

15,179 [6885]

 

 

 

 

MWB/NIH

Victaulic

13-115/8[4258]

14,489 [6572]

14,685 [6572]

14,929 [6772]

 

 

 

 

 

 

 

Flange

 

 

 

14,746 [6689]

14,768 [6689]

15,012 [6809]

 

 

 

 

 

 

 

 

 

MWB/MWB

Victaulic

 

 

 

 

14,668 [6653]

14,864 [6653]

15,108 [6853]

 

2 Pass

Flange

 

 

 

 

14,834 [6729]

15,030 [6729]

15,274 [6928]

 

 

 

 

 

 

 

NIH/NIH

Victaulic

13-65/16[4123]

 

 

 

14,319 [6495]

14,515 [6495]

14,759 [6695]

 

 

 

 

 

 

 

Flange

14-47/16[4380]

 

 

 

14,651 [6646]

14,847 [6646]

15,091 [6845]

 

 

 

 

 

 

 

 

NIH/MWB

Victaulic

14-23/16[4323]

 

 

 

14,498 [6576]

14,694 [6576]

14,938 [6776]

 

 

Flange

14-615/16[4443]

 

 

 

14,739 [6685]

14,935 [6685]

15,179 [6885]

 

 

 

 

 

 

 

 

MWB/NIH

Victaulic

14-213/16[4339]

 

 

 

14,489 [6572]

14,685 [6572]

14,929 [6772]

Opposite Ends

 

Flange

14-83/16[4475]

3-113/8[1210]

6-611/16

[1999]

14,746 [6689]

14,768 [6689]

15,012 [6809]

 

 

 

MWB/MWB

Victaulic

14-1011/16[4539]

14,668 [6653]

14,864 [6653]

15,108 [6853]

 

 

 

 

 

 

 

Flange

 

 

 

14,834 [6729]

15,030 [6729]

15,274 [6928]

 

 

NIH/NIH

Flange

14-55/8[4410]

 

 

 

14,828 [6726]

15,024 [6726]

15,268 [6925]

 

1 or

NIH/MWB

Flange

 

 

 

 

15,223 [6905]

14,768 [6896]

15,012 [6809]

 

3 Pass

MWB/NIH

Flange

14-1011/16[4539]

 

 

 

15,244 [6915]

15,440 [6894]

15,684 [7114]

 

 

MWB/MWB

Flange

 

 

 

 

15,581 [7067]

15,777 [7063]

16,021 [7267]

NOTES:

1.Operating weight includes weight of water, refrigerent, and oil.

2.30XW UNIT DIMENSIONS Denotes center of gravity.

3.Dimensions shown in ft-in. [mm] unless noted.

4.The recommended service clearance around the machine is 3 ft [914.4 mm].

5.Victaulic nozzles are standard on all units. A flow switch can be factory-installed in evaporator inlet victaulic nozzle.

6.Maximum fluid side pressure of condenser or evaporator is 150 psig [1034 kPa] (standard) or 300 psig [2068 kPa] (optional).

7.Operating weight includes weight of water, refrigerant, and oil.

12

Page 12
Image 12
Carrier 30XW325-400 manual Dimensions, a30-4745, Suction End, Discharge End, STANDARD 30XW UNIT DIMENSIONS