m. Time of day:
1)Display module, in conjunction with the microprocessor, must also be capable of displaying the output (results) of a ser- vice test. Service test shall verify opera- tion of every switch, thermistor, and compressor before chiller is started.
2)Diagnostics shall include the ability to review a list of the 30 most recent alarms with clear language descriptions of the alarm event. Display of alarm codes without the ability for clear lan- guage descriptions shall be prohibited.
3)An alarm history buffer shall allow the user to store no less than 30 alarm events with clear language descriptions, time and date stamp event entry.
4)The chiller controller shall include multi- ple connection ports for communicating with the local equipment network, the Carrier Comfort Network (CCN) sys- tem and the ability to access all chiller control functions from any point on the chiller.
5)The control system shall allow software upgrade without the need for new hard- ware modules.
J.Operating Characteristics:
Unit shall be capable of starting up with 95 F (35 C) entering fluid temperature to the evaporator.
K.Electrical Requirements:
1.Unit primary electrical power supply shall enter the unit at a single location.
2.Unit shall operate on
3.Control voltage shall be
L.Special Features:
Certain standard features are not applicable when the features designated by * are specified. For assis- tance in amending the specifications, contact your local Carrier Sales office.
*1.
Unit shall have a
2.Vibration Isolation:
Unit shall be supplied with
3.Control Power Transformer:
Unit shall be supplied with a
4.Temperature Reset Sensor:
Unit shall reset leaving chilled fluid temperature based on outdoor ambient temperature or space temperature when this sensor is installed.
* 5. Minimum Load Control:
Unit shall be equipped with
6.
7.
8.Energy Management Module:
A factory or field installed module shall provide the following energy management capabilities: 4 to 20 mA signals for leaving fluid temperature reset, cooling set point reset or demand limit control;
9.BACnet™ Translator Control:
Unit shall be supplied with
10.LON Translator Control:
Unit shall be supplied with
11.Navigator™ Hand Held Portable Display:
a.Portable hand held display module with a minimum of 4 lines and 20 characters per line, or clear English, Spanish, Portuguese or French language.
b.Display menus shall provide clear language descriptions of all menu items, operating modes, configuration points and alarm diag- nostics. Reference to factory codes shall not be accepted.
c.
d.Industrial grade coiled extension cord shall allow the display module to be moved around the chiller.
e.Magnets shall hold the display module to any sheet metal panel to allow
f.Display module shall have NEMA 4x housing.
g.Display shall have back light and contrast adjustment for easy viewing in bright sun- light or night conditions.
h.Raised surface buttons with positive tactile response.