Carrier manual Physical data cont, 30XW325-400 UNIT PHYSICAL DATA - SI

Models: 30XW325-400

1 32
Download 32 pages 43.36 Kb
Page 8
Image 8
Physical data (cont)

Physical data (cont)

30XW325-400 UNIT PHYSICAL DATA — SI

30XW UNIT SIZE

325

 

350

 

400

NOMINAL CAPACITY (kW)

1133

 

1206

 

1354

UNIT WEIGHT (kg) (Operating/Shipping)

6495/5971

 

6584/6064

 

6695/6119

COMPRESSORS

 

Semi-hermetic, twin screw

Compressor Speed (r/s)

 

58.3

 

 

Compressor Model Number (qty)

 

06TU483 (2)

 

06TU554 (2)

 

 

Unloading Type

 

 

Slide Valve

 

 

Minimum Step Capacity % (standard)

 

15%

 

 

Optional %

 

10%

 

 

Economizer

No

 

 

Yes

 

 

Temperature Relief Valve Connection (in. SAE Flare) (each circuit)

 

 

3/8

REFRIGERANT

 

 

HFC, R-134a

 

 

Charge (kg) Circuit A

117.9

 

 

122.5

 

 

Charge (kg) Circuit B

117.9

 

 

122.5

OIL

 

 

POE, SW-220

 

 

Charge (L) Circuit A

 

15.1

 

 

Charge (L) Circuit B

 

15.1

 

 

EVAPORATOR

 

 

 

 

 

Net Fluid Volume (L)

 

287.7

 

 

Maximum Refrigerant Pressure (kPa)

 

1517

 

 

Maximum Water Side Pressure (kPa)

 

 

 

 

 

Standard

 

1034

 

 

Optional

 

2068

 

 

Water Connections

 

 

 

 

 

Inlet and Outlet (in.)

 

 

 

 

 

1-Pass NIH or MWB Flange (optional)

 

6

 

 

1-Pass NIH Victaulic (optional)

 

8

 

 

2-Pass NIH or MWB Flange (optional)

 

6

 

 

2-Pass NIH Victaulic (standard)

 

8

 

 

2-Pass MWB Victaulic (optional)

 

6

 

 

3-Pass NIH or MWB Flange (optional)

 

6

 

 

3-Pass NIH Victaulic (optional)

 

8

 

 

Drain (in. NPT)

 

3/8

 

 

Relief Valve Connection (in. NPTF)

 

3/4

 

 

Quantity Per Circuit

 

1

 

 

Relief Valve Setting (kpa)

 

1517

 

 

Flow Rate (kg air/min)

 

14.38

 

 

CONDENSER

 

 

 

 

 

Net Fluid Volume (L)

 

312.7

 

 

Maximum Refrigerant Pressure (kPa)

 

 

 

 

 

Standard Condenser

 

1517

 

 

Heat Machine

 

2068

 

 

Maximum Water Side Pressure (kPa)

 

 

 

 

 

Standard

 

1034

 

 

Optional

 

2068

 

 

Heat Machine

 

2068

 

 

Water Connections

 

 

 

 

 

Inlet and Outlet (in.)

 

 

 

 

 

1-Pass NIH or MWB Flange (optional)

 

6

 

 

1-Pass NIH Victaulic (optional)

 

8

 

 

2-Pass NIH or MWB Flange (optional)

 

6

 

 

2-Pass NIH Victaulic (standard)

 

8

 

 

2-Pass MWB Victaulic (optional)

 

6

 

 

Drain (in. NPT)

 

3/8

 

 

Relief Valve Connection (in. NPTF) (Standard/Heat Machine)

 

3/4 / 3/4

 

 

Quantity Per Circuit

 

2/2

 

 

Relief Valve Setting (kpa)

 

1517/2068

 

 

Flow Rate (kg air/min)

 

14.38/21.1

 

 

Temperature Relief Valve Connection (in. SAE Flare)

 

1/4

 

 

Discharge Line (Qty per Circuit)

 

1

 

 

Liquid Line (Qty per Circuit)

 

1

 

 

CHASSIS DIMENSIONS (mm)

 

 

 

 

 

Length

 

4057.7

 

 

Width

 

1203.3

 

 

Height

 

1998.7

 

 

LEGEND

HFC — Hydrofluorocarbon

MWB — Marine Waterbox

NIH — Nozzle-In-Head

NPTF — National Pipe Thread Female

POE — Polyolester

SAE — Society of Automotive Engineers

8

Page 8
Image 8
Carrier manual Physical data cont, 30XW325-400 UNIT PHYSICAL DATA - SI