Carrier 30XW325-400 manual Capacity ratings

Models: 30XW325-400

1 32
Download 32 pages 43.36 Kb
Page 6
Image 6
Capacity ratings

Capacity ratings

 

CAPACITY

INPUT

EVAPORATOR

EVAPORATOR

CONDENSER

CONDENSER

FULL LOAD

 

30XW

FLOW

PRESSURE DROP

FLOW

PRESSURE DROP

IPLV

 

 

UNIT SIZE

Tons

Output

POWER

gpm

L/s

Ft of

kPa

gpm

L/s

Ft of

kPa

EFFICIENCY

(kW/Ton)

 

(kW)

(kW)

Water

Water

(kW/Ton)

 

 

 

 

 

 

 

 

 

 

 

 

325

322

1132.5

204.8

773

48.8

15.6

46.5

967

61.0

10.9

32.5

0.636

0.468

350

343

1206.3

215.7

824

52.0

17.5

52.2

1029

64.9

12.3

36.7

0.629

0.471

400

385

1354.0

242.8

924

58.3

21.5

64.1

1155

72.9

15.2

45.3

0.631

0.474

LEGEND

AHRI — Air Conditioning, Heating and Refrigeration Institute

IPLV — Integrated Part Load Value

NOTES:

1.Certified in accordance with AHRI Standard 550/590 at standard rating conditions.

2.Standard rating conditions are as follows:

Evaporator Conditions:

Leaving Water Temperature: 44 F (6.7 C)

Flow:2.4 gpm per ton (0.043 L/s per kW) Condenser Conditions:

Entering Water Temperature:85 F (29.4 C)

Flow:

3.0 gpm per ton (0.054 L/s per kW)

Fouling Factor (Evaporator):

0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W) Fouling Factor (Condenser):

0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W)

3.IPLV is a single number part-load efficiency value calculated from the system full-load efficiency values and corrected for a typical building air-conditioning application.

4.Contact Carrier for custom ratings.

5.Data shown for standard chiller with 2 pass, nozzle-in-head (NIH) waterboxes.

6

Page 6
Image 6
Carrier 30XW325-400 manual Capacity ratings