Capacity ratings
| CAPACITY | INPUT | EVAPORATOR | EVAPORATOR | CONDENSER | CONDENSER | FULL LOAD |
| ||||||
30XW | FLOW | PRESSURE DROP | FLOW | PRESSURE DROP | IPLV | |||||||||
|
| |||||||||||||
UNIT SIZE | Tons | Output | POWER | gpm | L/s | Ft of | kPa | gpm | L/s | Ft of | kPa | EFFICIENCY | (kW/Ton) | |
| (kW) | (kW) | Water | Water | (kW/Ton) |
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
325 | 322 | 1132.5 | 204.8 | 773 | 48.8 | 15.6 | 46.5 | 967 | 61.0 | 10.9 | 32.5 | 0.636 | 0.468 | |
350 | 343 | 1206.3 | 215.7 | 824 | 52.0 | 17.5 | 52.2 | 1029 | 64.9 | 12.3 | 36.7 | 0.629 | 0.471 | |
400 | 385 | 1354.0 | 242.8 | 924 | 58.3 | 21.5 | 64.1 | 1155 | 72.9 | 15.2 | 45.3 | 0.631 | 0.474 |
LEGEND
AHRI — Air Conditioning, Heating and Refrigeration Institute
IPLV — Integrated Part Load Value
NOTES:
1.Certified in accordance with AHRI Standard 550/590 at standard rating conditions.
2.Standard rating conditions are as follows:
Evaporator Conditions:
Leaving Water Temperature: 44 F (6.7 C)
Flow:2.4 gpm per ton (0.043 L/s per kW) Condenser Conditions:
Entering Water Temperature:85 F (29.4 C)
Flow: | 3.0 gpm per ton (0.054 L/s per kW) |
Fouling Factor (Evaporator):
0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W) Fouling Factor (Condenser):
0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W)
3.IPLV is a single number
4.Contact Carrier for custom ratings.
5.Data shown for standard chiller with 2 pass,