Controls (cont)
•Evaporator entering fluid temperature (T2)
•Suction gas temperature (T4 - Circuit A, T7 - Circuit B)
•Economizer gas temperature (T5 - Circuit A, T11 - Circuit B) (sizes 350, 400 only)
•Space temperature (T8)
•Discharge gas temperature (T9 - Circuit A, T10 - Circuit B)
•Condenser entering fluid temperature (T12)
•Condenser leaving fluid temperature (T13)
•Compressor motor temperature
There are 3 (size 325) or 4 (sizes 350, 400) refrigerant pressure transducers used in each circuit for sensing suc- tion, discharge, oil, and economizer (sizes 350, 400) pres- sure. The microprocessor uses these inputs to control capacity.
•Saturated condensing temperature
•Evaporator saturation temperature
Electronic expansion valve (EXV) — The EXV con- trols refrigerant flow to the evaporator for different operat- ing conditions by varying an orifice size to increase or decrease the flow area through the valve based on micro- processor input. The orifice is positioned by a stepper motor through approximately 3,600 discrete steps and is monitored every 3 seconds.
Safeties
Abnormal conditions — All control safeties in the chiller operate through compressor protection board, control relays or the chiller microprocessor. Loss of feedback sig- nal to the MBB will cause the compressor(s) to shut down. For other safeties, the microprocessor makes appropriate decision to shut down a compressor due to a safety trip or bad sensor reading and displays the appropriate failure code on the display. Chiller holds in safety mode until reset; it then reverts to normal control when the unit is reset.
Compressor
Loss of flow protection — This feature will shut off the chiller if the detected flow is below the configured mini- mum flow rate. Thermal dispersion flow switches are installed in 30XW chillers to confirm evaporator flow.
Sensor failures — The microprocessor monitors tem- perature and pressure sensors to ensure readings are within the expected range. Loss of communication to a sensor or readings outside of the expected range will prompt corrective action.
Other safeties — Other safety features include electric overload, thermal overload protection, oil pressure, loss of refrigerant charge, loss of phase protection, reverse rotation protection (prevents compressor start), current imbalance, and ground current.
Demand limit function — This function can be used to limit the total power draw of the chiller to a
The microprocessor can control the number of compres- sors operating and their operating capacity to limit power consumption to the user specified value.
Diagnostics — The microprocessor includes a service test feature that displays the condition of each sensor and switch in the chiller and allows the observer to check for proper operation of the compressors. Refer to the Con- trols, Start Up, Operation, Service and Troubleshooting guide for further information.
Default settings — To facilitate quick
Additional information — Detailed information on con- trols and operation is available in the Controls,
20