Selection procedure
Carrier’s packaged selection program provides quick, easy selection of Carrier’s
Before selecting a chiller, consider the following points: Leaving water (fluid) temperature (LWT)
•The LWT must be at least 40 F (4.4 C) or greater.
•If the LWT requirement is greater than 60 F (15.5 C), a mixing loop is required.
Entering water (fluid) temperature (EWT)
•If the EWT requirement is greater than 70 F (21.1 C), a mixing loop is required. The EWT should not exceed 70 F (21.1 C) for extended operation. Pulldown can be accomplished from 95 F (35 C).
Evaporator flow rate or evaporator
•The evaporator
•For larger or smaller
Evaporator pressure drop:
•A high evaporator pressure drop can be expected when the evaporator
•The
Condenser pressure drop:
•A high condenser pressure drop can be expected when the condenser
Series chillers:
•
Water quality, fouling factor:
•Poor water quality can increase the required evaporator fouling factor.
•Higher than standard fouling factors lead to lower capacity and higher input kW from a given chiller size compared to running the same application with better water quality (and lower fouling factors).
Temperature reset:
•Return water (standard)
•Outside air temperature (standard)
•Space temperature (accessory sensor required)
•4 to 20 mA (requires an energy management module)
Demand limit:
•
•4 to 20 mA (requires an energy management module)
•CCN Loadshed
Performance data
EVAPORATOR AND CONDENSER FLOW RATES
|
|
| EVAPORATOR |
|
|
| CONDENSER |
|
|
| NOMINAL |
| ||||
|
| Leaving Fluid/Entering Fluid | Minimum Entering | Maximum Leaving |
|
|
|
| ||||||||
|
| Minimum | Maximum |
| Fluid |
| Fluid | Evaporator | Condenser | |||||||
30XW UNIT | 40 F (4.4 C)/ | 60 F (15.6 C)/ | 65 F (18.3 C) | 118 F (47.8 C)* | ||||||||||||
|
|
|
| |||||||||||||
45 F (7.2 C) | 70 F (21.1 C) |
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| Minimum | Maximum | Minimum | Maximum | Nominal | Nominal | |||||||||
|
| Flow Rate | Flow Rate | Flow Rate | Flow Rate | Flow Rate | Flow Rate | |||||||||
|
| GPM | L/s | GPM | L/s | GPM |
| L/s | GPM |
| L/s | GPM | L/s | GPM | L/s | |
| Two pass | 411 | 25.9 | 1481 | 93.4 | 494 |
| 31.1 | 1974 |
| 124.5 | 790 | 49.8 | 987 | 62.3 | |
325 | One pass | 790 | 49.8 | 3126 | 197.2 | 987 |
| 62.3 | 3290 |
| 207.6 | 790 | 49.8 | 987 | 62.3 | |
| Three pass | 247 | 15.6 | 987 | 62.3 | — |
| — | — |
| — | 790 | 49.8 | — | — | |
| Two pass | 433 | 27.3 | 1557 | 98.2 | 519 |
| 32.7 | 2076 |
| 131.0 | 830 | 52.4 | 1038 | 65.5 | |
350 | One pass | 830 | 52.4 | 3287 | 207.4 | 1038 |
| 65.5 | 3460 |
| 218.3 | 830 | 52.4 | 1038 | 65.5 | |
| Three pass | 260 | 16.4 | 1038 | 65.5 | — |
| — | — |
| — | 830 | 52.4 | — | — | |
| Two pass | 486 | 30.7 | 1751 | 110.4 | 584 |
| 36.8 | 2334 |
| 147.3 | 934 | 58.9 | 1167 | 73.6 | |
400 | One pass | 934 | 58.9 | 3696 | 233.1 | 1167 |
| 73.6 | 3890 |
| 245.4 | 934 | 58.9 | 1167 | 73.6 | |
| Three pass | 292 | 18.4 | 1167 | 73.6 | — |
| — | — |
| — | 934 | 58.9 | — | — |
*Maximum condenser fluid temperature shown for standard condensing option. Heat machine option may have leaving fluid temperatures up to 140 F (60 C).
15