CHECK VOLTAGE IMBALANCE

 

 

 

 

 

 

 

 

 

 

 

 

LINE-TO-LINE VOLTS:

AB

 

V

AC

 

 

 

V

BC

 

 

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

 

 

 

V

V

 

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

 

 

 

 

%

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

 

 

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

C. Start-Up

CHECK EVAPORATOR FAN SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE

SUCTION PRESSURE

SUCTION LINE TEMP

DISCHARGE PRESSURE

DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP

LEAVING OUTDOOR UNIT AIR TEMP

INDOOR UNIT ENTERING AIR DB TEMP

INDOOR UNIT ENTERING AIR WB TEMP

INDOOR UNIT LEAVING AIR DB TEMP

INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

INDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

COMPRESSOR AMPS (L1/L2/L3)

 

 

 

 

/

 

/

 

 

 

/

 

/

 

 

 

 

 

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING

 

 

OIL LEVEL AT 1¤8 TO 1¤3 FULL?

(Y/N)

 

 

 

 

 

 

 

 

 

 

NOTES: