Table 4 Ð Electrical Data, Standard Motors

 

 

VOLTAGE

 

FAN MOTOR

POWER SUPPLY

 

UNIT

V*-PH-HZ

LIMITS

Hp

 

FLA

Minimum

 

MOCP

 

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187-253

1.3

 

7.6

9.5

 

15

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RM

460-3-60

414-528

2.4

 

2.6

3.3

 

15

007

575-3-60

518-632

1.0

 

1.35

1.7

 

15

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-1-60

187-253

2.4

 

11.0

13.8

 

20

40RM

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

460-3-60

414-528

2.4

 

2.6

3.3

 

15

40RMQ

 

 

40RMS

575-3-60

518-632

2.0

 

2.4

3.0

 

15

008

 

 

 

 

 

 

 

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

 

 

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-1-60

187-253

2.4

 

11.0

13.8

 

20

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RMS

460-3-60

414-528

2.4

 

2.6

3.3

 

15

010

575-3-60

518-632

2.0

 

2.4

3.0

 

15

 

230-3-50

207-253

2.4

 

5.8

7.3

 

15

 

400-3-50

360-440

2.4

 

2.6

3.3

 

15

 

208/230-3-60

187-253

2.4

 

5.8

7.3

 

15

40RM

460-3-60

414-528

2.4

 

2.6

3.3

 

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

2.0

 

2.4

3.0

 

15

40RMS

 

 

012

230-3-50

207-253

2.9

 

7.5

9.4

 

15

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

2.9

 

7.5

9.4

 

15

40RM

460-3-60

414-528

2.9

 

3.4

4.3

 

15

40RMS

575-3-60

518-632

3.0

 

3.8

4.8

 

15

014

 

 

 

 

 

 

 

 

230-3-50

207-253

2.9

 

7.5

9.4

 

15

 

 

 

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

3.7

 

10.6

13.3

 

20

40RM

460-3-60

414-528

3.7

 

4.8

6.0

 

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

3.0

 

3.8

4.8

 

15

40RMS

 

 

230-3-50

207-253

2.9

 

7.5

9.4

 

15

016

 

 

 

400-3-50

360-440

2.9

 

3.4

4.3

 

15

 

208/230-3-60

187-253

5.0

 

15.2/14.4

19.0/18.0

 

30/30

40RM

460-3-60

414-528

5.0

 

7.2

9.0

 

15

40RMS

575-3-60

518-632

5.0

 

5.6

7.0

 

15

024

 

 

 

 

 

 

 

 

230-3-50

207-253

5.0

 

14.4

18.0

 

30

 

 

 

 

400-3-50

360-440

5.0

 

7.2

9.0

 

15

 

208/230-3-60

187-253

7.5

 

22.0/21.0

27.5/26.3

 

45/45

40RM

460-3-60

414-528

7.5

 

10.5

13.1

 

20

40RMS

575-3-60

518-632

7.5

 

7.6

9.5

 

15

028

 

 

 

 

 

 

 

 

230-3-50

207-253

7.5

 

21.0

26.3

 

45

 

 

 

 

400-3-50

360-440

7.5

 

10.5

13.1

 

20

 

208/230-3-60

187-253

10.0

 

26.4/25.0

33.0/31.3

 

55/55

40RM

460-3-60

414-528

10.0

 

12.5

15.6

 

25

40RMS

575-3-60

518-632

10.0

 

9.6

12.0

 

20

034

 

 

 

 

 

 

 

 

230-3-50

207-253

10.0

 

25.0

31.3

 

55

 

 

 

 

440-3-50

360-440

10.0

 

12.5

15.6

 

25

 

 

 

 

 

 

 

 

 

See Legend and Notes on page 21.

20

Page 20
Image 20
Carrier 40RMQ, 40RMS Electrical Data, Standard Motors, Voltage FAN Motor Power Supply Unit PH-HZ, Fla, Mocp