Legend and Notes for Table 10A and 10B

LEGEND

Bhp Ð Brake Horsepower Input to Fan

ESP Ð External Static Pressure

NOTES:

1.Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 034; 1200 rpm for all other sizes.

2.Fan performance is based on deductions for wet coil, clean 2-in. ®lters, and unit casing. See right for factory-supplied ®lter pres- sure drop.

3.Refer to fan motor and drive tables for additional data.

Factory-Supplied Filter Pressure Drop Ð English

UNIT

AIRFLOW

PRESSURE DROP

(Cfm)

(in. wg)

 

40RM

1,800

0.05

2,400

0.08

007

3,000

0.11

 

40RM

2,250

0.07

40RMQ

3,000

0.11

40RMS

3,750

0.15

008

 

 

40RMS

2,550

0.09

3,400

0.13

010

4,250

0.18

 

40RM

3,000

0.11

40RMQ

4,000

0.17

40RMS

5,000

0.23

012

 

 

40RM

3,750

0.06

40RMS

5,000

0.10

014

6,250

0.13

40RM

4,500

0.08

40RMQ

6,000

0.12

40RMS

7,500

0.17

016

 

 

40RM

6,000

0.12

40RMS

8,000

0.19

024

10,000

0.26

40RM

7,500

0.15

40RMS

10,000

0.22

028

12,500

0.30

40RM

9,000

0.19

40RMS

12,000

0.29

034

15,000

0.40

36

Page 36
Image 36
Carrier 40RMQ, 40RMS installation instructions Unit Airflow Pressure Drop