Carrier 48TF004-007 specifications 48TF006 5 TONS - ALTERNATE MOTOR BELT DRIVE

Models: 48TF004-007

1 52
Download 52 pages 21.55 Kb
Page 32
Image 32
Manual background

Table 26 — Fan Performance 48TF006 — Horizontal Discharge Units, Alternate Motor

48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.1

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

730

0.34

357

789

 

0.40

420

896

0.53

557

990

0.67

704

1072

0.83

872

1153

1.00

1051

1600

770

0.40

420

826

 

0.46

483

931

0.61

641

1020

0.75

788

1101

0.91

956

1178

1.09

1145

1700

811

0.47

494

865

 

0.54

567

966

0.69

725

1051

0.84

883

1133

1.01

1061

1205

1.18

1240

1800

852

0.55

578

905

 

0.62

651

1002

0.78

820

1084

0.93

977

1163

1.10

1156

1235

1.29

1355

1900

894

0.54

567

945

 

0.72

757

1037

0.88

925

1119

1.04

1093

1194

1.21

1271

1266

1.40

1471

2000

936

0.74

778

984

 

0.82

862

1072

0.98

1030

1154

1.16

1219

1226

1.33

1397

1297

1.53

1608

2100

978

0.85

893

1024

 

0.93

977

1108

1.10

1156

1192

1.29

1355

1259

1.47

1545

1327

1.66

1744

2200

1021

0.97

1019

1064

 

1.05

1103

1145

1.22

1282

1225

1.43

1503

1294

1.62

1702

1359

1.80

1902

2300

1064

1.10

1156

1104

 

1.18

1240

1183

1.36

1429

1260

1.57

1650

1330

1.78

1870

1392

1.97

2070

2400

1107

1.24

1303

1145

 

1.32

1387

1222

1.45

1524

1296

1.73

1818

1365

1.94

2038

1426

2.15

2259

2500

1150

1.39

1460

1186

 

1.48

1555

1262

1.68

1765

1331

1.89

1986

1400

2.12

2227

1461

2.34

2459

 

 

 

 

 

 

 

 

 

 

 

 

48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

 

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

 

 

 

1500

1221

1.17

1229

1256

 

1.30

1366

1283

1.32

1387

1303

1.22

1282

 

 

 

 

 

 

1600

1252

1.27

1334

1311

 

1.45

1524

1340

1.58

1660

1330

1.61

1692

 

 

 

 

 

 

1700

1278

1.37

1439

1345

 

1.57

1650

1397

1.76

1849

1424

1.89

1986

 

 

 

 

 

 

1800

1303

1.48

1555

1371

 

1.69

1776

1433

1.90

1996

1480

2.09

2196

 

 

 

 

 

 

1900

1330

1.59

1671

1396

 

1.80

1902

1460

2.03

2133

1517

2.25

2364

 

 

 

 

 

 

2000

1362

1.73

1818

1422

 

1.94

2038

1485

2.16

2270

1544

2.40

2522

 

 

 

 

 

 

2100

1393

1.87

1965

1452

 

2.08

2185

1510

2.31

2427

1570

2.55

2674

 

 

 

 

 

 

2200

1423

2.02

2122

1483

 

2.24

2354

 

 

 

1594

2.71

2821

 

 

 

 

 

 

1538

2.46

2585

 

 

 

 

 

 

2300

1454

2.18

2291

1515

 

2.41

2532

1571

2.64

2758

1623

2.88

2976

 

 

 

 

 

 

2400

1485

2.36

2480

1544

 

2.59

2721

1604

2.84

2947

1657

3.07

3152

 

 

 

 

 

 

2500

 

 

 

1574

 

2.78

2905

1633

3.03

3134

1692

3.28

3345

 

 

 

 

 

 

1518

2.55

2679

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 900 to 1300 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Manual backgroundManual background indicates field-supplied motor and drive are required.

3.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 1.30 for single-phase units and 2.40 for 3-phase units and the maximum continuous watts are 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for additional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

6.Interpolation is permissible. Do not extrapolate.

32

Page 32
Image 32
Carrier 48TF004-007 specifications 48TF006 5 TONS - ALTERNATE MOTOR BELT DRIVE