Carrier 48TF004-007 specifications Cooling Service Analysis

Models: 48TF004-007

1 52
Download 52 pages 21.55 Kb
Page 45
Image 45

Table 34 — Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and condenser fan

Power failure.

Call power company.

will not start.

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

 

 

Defective thermostat, contactor, transformer, or

Replace component.

 

control relay.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room temperature.

Compressor will not start but

Faulty wiring or loose connections in compressor

Check wiring and repair or replace.

condenser fan runs.

circuit.

 

 

Compressor motor burned out, seized, or internal

Determine cause. Replace compressor.

 

overload open.

 

 

Defective run/start capacitor, overload, start relay.

Determine cause and replace.

 

One leg of three-phase power dead.

Replace fuse or reset circuit breaker. Determine cause.

Compressor cycles (other than

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and recharge to

normally satisfying thermostat).

 

nameplate.

 

Defective compressor.

Replace and determine cause.

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked condenser.

Determine cause and correct.

 

Defective run/start capacitor, overload, or start

Determine cause and replace.

 

relay.

 

 

Defective thermostat.

Replace thermostat.

 

Faulty condenser-fan motor or capacitor.

Replace.

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor operates

Dirty air filter.

Replace filter.

continuously.

 

 

Unit undersized for load.

Decrease load or increase unit size.

 

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak; repair and recharge.

 

Leaking valves in compressor.

Replace compressor.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive head pressure.

Dirty air filter.

Replace filter.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharged.

Recover excess refrigerant.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling.

Determine cause and correct.

Head pressure too low.

Low refrigerant charge.

Check for leaks; repair and recharge.

 

Compressor valves leaking.

Replace compressor.

 

Restriction in liquid tube.

Remove restriction.

Excessive suction pressure.

High head load.

Check for source and eliminate.

 

Compressor valves leaking.

Replace compressor.

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction pressure too low.

Dirty air filter.

Replace filter.

 

Low refrigerant charge.

Check for leaks; repair and recharge.

 

Metering device or low side restricted.

Remove source of restriction.

 

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if

 

 

necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Outdoor ambient below 25 F.

Install low-ambient kit.

Evaporator fan will not shut off.

Time off delay not finished.

Wait for 30-second off delay.

Compressor makes excessive

Compressor rotating in wrong direction.

Reverse the 3-phase power leads as described in the

noise (48TF007 scroll only).

 

Start-Up section on page 36.

45

Page 45
Image 45
Carrier 48TF004-007 specifications Cooling Service Analysis