Carrier 48TF004-007 specifications 48TF004 3 TONS - STANDARD MOTOR DIRECT DRIVE

Models: 48TF004-007

1 52
Download 52 pages 21.55 Kb
Page 28
Image 28
Manual background

Table 19 — Fan Performance 48TF004 — Horizontal Discharge Units, Standard Motor

48TF004 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

(Cfm)

 

 

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

Esp

Bhp

Watts

Esp

 

Bhp

 

Watts

900

0.54

0.21

253

0.57

 

0.23

 

277

0.55

0.26

307

0.60

 

0.31

 

363

1000

0.49

0.23

270

0.51

 

0.25

 

292

0.52

0.27

321

0.53

 

0.32

 

374

1100

0.43

0.24

287

0.45

 

0.26

 

307

0.46

0.28

335

0.49

 

0.33

 

385

1200

0.39

0.26

304

0.40

 

0.27

 

323

0.38

0.29

349

0.43

 

0.34

 

397

1300

0.33

0.27

321

0.35

 

0.29

 

338

0.35

0.31

364

0.36

 

0.34

 

408

1400

0.26

0.29

338

0.28

 

0.30

 

354

0.29

0.32

378

 

 

1500

0.21

0.30

355

0.23

 

0.31

 

369

0.24

0.33

392

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Esp — External Static Pressure (in. wg)

FIOP — Factory-Installed Option

NOTES:

1.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Table 6 — Motor Data for Additional information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

Table 20 — Fan Performance 48TF004 — Horizontal Discharge Units, Alternate Motor

48TF004 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.1

 

 

0.2

 

 

0.3

 

 

0.4

 

 

0.5

 

 

0.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

526

0.06

70

584

0.08

99

656

 

0.12

139

734

0.22

219

818

0.25

269

875

0.27

269

1000

570

0.09

109

627

0.13

149

738

 

0.19

189

800

0.26

259

848

0.29

288

895

0.31

308

1100

614

0.13

149

670

0.16

189

758

 

0.23

229

812

0.29

288

863

0.32

308

914

0.35

348

1200

658

0.16

189

710

0.23

229

780

 

0.28

279

840

0.32

318

889

0.36

358

938

0.40

398

1300

703

0.20

239

752

0.27

269

808

 

0.32

318

868

0.37

368

916

0.41

408

963

0.45

448

1400

725

0.29

288

776

0.31

308

845

 

0.38

378

891

0.42

418

937

0.47

467

983

0.51

507

1500

755

0.33

328

816

0.38

378

870

 

0.43

428

924

0.48

477

969

0.53

527

1014

0.58

577

 

 

 

 

 

 

 

 

 

 

 

48TF004 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.7

 

 

0.8

 

 

0.9

 

 

1.0

 

 

1.1

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

924

0.32

308

953

0.35

348

989

 

0.38

388

1028

0.42

438

1074

0.45

487

1120

0.50

537

1000

936

0.35

348

977

0.39

388

1020

 

0.44

438

1064

0.48

477

1124

0.52

537

1185

0.55

597

1100

960

0.39

388

1005

0.43

428

1052

 

0.49

487

1100

0.52

527

1163

0.56

587

1225

0.60

647

1200

988

0.45

448

1038

0.50

497

1076

 

0.53

527

1136

0.59

577

1201

0.61

647

1266

0.64

716

1300

1012

0.51

507

1061

0.56

557

1094

 

0.61

607

1172

0.65

647

1239

0.69

716

1306

0.72

786

1400

1027

0.56

557

1071

0.60

597

1108

 

0.67

666

1208

0.70

706

1278

0.75

786

1347

0.79

865

1500

1056

0.63

627

1097

0.68

676

1117

 

0.70

696

1245

0.74

776

1315

0.80

865

1385

0.85

955

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Motor drive range is 760 to 1000 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Values include losses for filters, unit casing, and wet coils. See Table 7 for accessory/FIOP static pressure information.

3.Maximum continuous bhp is 1.00 and maximum continuous watts are 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confi- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. See Table 6 — Motor Data for additional information.

4.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.

5.Interpolation is permissible. Do not extrapolate.

28

Page 28
Image 28
Carrier 48TF004-007 specifications 48TF004 3 TONS - STANDARD MOTOR DIRECT DRIVE