Carrier specifications Physical Data - 48TF004-007cont

Models: 48TF004-007

1 52
Download 52 pages 21.55 Kb
Page 6
Image 6

Table 1 — Physical Data — 48TF004-007 (cont)

UNIT SIZE 48TF

 

 

E/F/M/N004

D/E/F/L/M/N005

 

D/E/F/L/M/N006

D/E/F007

FURNACE SECTION

 

 

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

 

 

Temp (F)††

 

 

195

195

 

195

195

Burner Orifice Diameter

 

 

 

 

 

 

(in. ...drill size)

 

 

 

 

 

 

 

Natural Gas

Std

TFD

.113...33

 

.113...33

.113...33

 

 

TFE

.113...33

.113...33

 

.113...33

.113...33

 

 

TFF

.113...33

.129...30

 

.129...30

.129...30

 

 

TFL

.102...38

 

.102...38

 

 

TFM

.102...38

.102...38

 

.102...38

 

 

TFN

.102...38

.116...32

 

.116...32

Liquid Propane

Alt

TFD

.089...43

 

.089...43

.089...43

 

 

TFE

.089...43

.089...43

 

.089...43

.089...43

 

 

TFF

.089...43

.102...38

 

.102...38

.102...38

 

 

TFL

.082...45

 

.082...45

 

 

TFM

.082...45

.082...45

 

.082...45

Thermostat Heat Anticipator

TFN

.082...45

.089...43

 

.089...43

 

 

 

 

 

 

Setting (amps)

 

 

 

 

 

 

 

208/230 v and 575

Stage 1

 

.14

.14

 

.14

.14

 

Stage 2

 

.14

.14

 

.14

.14

460 v

Stage 1

 

.14

.14

 

.14

.14

 

Stage 2

 

.14

.14

 

.14

.14

Gas Input (Btuh)

Stage 1

TFD

72,000

 

72,000

72,000

 

 

TFE

72,000

115,000

 

115,000

115,000

 

 

TFF

82,000

120,000

 

120,000

120,000

 

 

TFL

60,000

 

60,000

 

 

TFM

60,000

90,000

 

90,000

 

 

TFN

90,000

120,000

 

120,000

 

Stage 2

TFF

115,000

150,000

 

150,000

150,000

 

(3-phase units)

 

Efficiency (Steady

 

 

 

 

 

 

 

 

 

 

 

 

 

State) (%)

 

 

80

80

 

80

80

Temperature Rise Range

TFD

25-55

 

25-55

25-55

 

 

TFE

25-55

35-65

 

35-65

35-65

 

 

TFF

55-85

50-80

 

50-80

50-80

 

 

TFL

20-50

 

20-50

 

 

TFM

20-50

30-60

 

30-60

Manifold Pressure (in. wg)

TFN

30-60

40-70

 

40-70

 

 

 

 

 

 

Natural Gas

Std

 

3.5

3.5

 

3.5

3.5

Liquid Propane

Alt

 

3.5

3.5

 

3.5

3.5

Gas Valve Quantity

 

 

1

1

 

1

1

Gas Valve Pressure Range

 

 

 

 

 

 

Psig

 

 

0.180-0.487

0.180-0.487

 

0.180-0.487

0.180-0.487

in. wg

 

 

5.0-13.5

5.0-13.5

 

5.0-13.5

5.0-13.5

Field Gas Connection

 

 

1/

1/

 

1/

1/

Size (in.)

 

 

 

 

 

 

2

2

 

2

2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

Standard Compressor

 

 

 

450 ± 50

 

 

500 ± 50

Internal Relief (Differential)

 

 

 

 

 

 

Cutout

 

 

 

428

 

 

428

Reset (Auto.)

 

 

 

320

 

 

320

LOSS-OF-CHARGE (LOW-

 

 

 

7 ± 3

 

PRESSURE SWITCH) (psig)

 

 

 

 

Cutout

 

 

 

 

 

 

 

Reset (Auto.)

 

 

 

 

22 ± 7

 

FREEZE PROTECTION

 

 

 

 

 

 

 

THERMOSTAT (F)

 

 

 

 

 

 

 

Opens

 

 

 

 

30 ± 5

 

Closes

 

 

 

 

45 ± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

Quantity...Size (in.)

 

 

 

1...20 x 24 x 1

 

RETURN-AIR FILTERS

 

 

 

Throwaway

 

Quantity...Size (in.)

 

 

 

2...16 x 25 x 2

 

 

 

LEGEND

Al

Aluminum

Bhp

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local representative for details about coated fins.

†Weight of 14-in. roof curb. **Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.

Single-phase units have a single-stage gas valve. The heating input values are as follows:

48TFF004, 115,000 Btuh 48TFF005, 150,000 Btuh 48TFF006, 150,000 Btuh

NOTE: High-static motor not available on single-phase units.

6

Page 6
Image 6