Table 2 — Electrical Data

UNIT

NOMINAL

IFM

VOLTAGE

COMPRESSOR

 

OFM

 

IFM

COMBUSTION

POWER

DISCONNECT

RANGE

 

(ea)

 

(ea)

 

FAN MOTOR

SUPPLY

SIZE*

48TF

V-Ph-Hz

TYPE

 

 

 

FLA

Min

Max

RLA

 

LRA

Qty

Hp

FLA

FLA

MCA

MOCP†

FLA

LRA

 

 

 

 

 

 

208/230-1-60

Std

187

254

16.2

 

96.0

1

1/

1.4

3.5

.6

24.5/24.5

30/30

23/23

106/106

 

 

 

 

 

 

 

 

 

 

Alt

 

 

 

 

 

 

4

 

4.9

 

26.6/26.6

35/35

26/26

111/111

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

17.7/17.7

25/25

17/17

85/85

 

208/230-3-60

Alt

187

254

10.2

 

75.0

1

1/

1.4

4.9

.6

19.1/19.1

25/25

19/19

90/90

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

5.2

 

19.4/19.4

25/25

19/19

109/109

004

 

Std

 

 

 

 

 

 

 

 

1.3

 

7.6

15

7

48/48

 

460-3-60

Alt

414

508

4.4

 

40.0

1

1/

0.8

2.1

.3

8.4

15

8

48/48

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

8.9

15

9

57/57

 

 

Std

 

 

 

 

 

 

 

 

1.3

 

6.3

15

7

35

 

575-3-60

Alt

518

632

3.7

 

31.0

1

1/

0.8

2.1

.3

6.9

15

8

37

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

7.3

15

7

45

 

208/230-1-60

Std

187

254

23.3

 

118.0

1

1/

1.4

3.5

.6

34.0/34.0

40/40

32/32

129/129

 

 

 

 

 

 

 

 

 

 

Alt

 

 

 

 

 

 

4

 

4.9

 

35.4/35.4

45/45

34/34

133/133

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

24.2/24.2

30/30

23/23

101/101

 

208/230-3-60

Alt

187

254

15.4

 

90.0

1

1/

1.4

4.9

.6

25.6/25.6

30/30

25/25

105/105

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

5.2

 

25.9/25.9

30/30

25/25

124/124

005

 

Std

 

 

 

 

 

 

 

 

1.8

 

13.0

20

13

51

 

460-3-60

Alt

414

508

8.3

 

45.0

1

1/

0.8

2.1

.3

13.3

20

13

53

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

13.8

20

13

62

 

 

Std

 

 

 

 

 

 

 

 

1.8

 

10.1

15

10

41

 

575-3-60

Alt

518

632

6.4

 

36.0

1

1/

0.8

2.1

.3

10.3

15

11

42

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

2.6

 

10.7

15

10

50

 

208/230-1-60

Std

187

254

28.8

 

147

1

1/

1.4

5.9

.6

43.3/43.3

60/60

42/42

161/161

 

 

 

 

 

 

 

 

 

 

Alt

 

 

 

 

 

 

4

 

6.6

 

44.0/44.0

60/60

42/42

184/184

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

5.9

 

27.3/27.3

35/35

29/29

128/128

 

208/230-3-60

Alt

187

254

16.3

 

114

1

1/

1.4

5.2

.6

26.6/26.6

35/35

26/26

148/148

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

7.5

 

28.9/28.9

35/35

29/29

174/174

006

 

Std

 

 

 

 

 

 

 

 

3.1

 

13.2

20

13

72

 

460-3-60

Alt

414

508

7.4

 

64

1

1/

0.8

2.6

.3

12.7

15

12

81

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

3.4

 

13.5

20

13

94

 

 

Std

 

 

 

 

 

 

 

 

3.1

 

10.9

15

11

58

 

575-3-60

Alt

518

632

6.2

 

62

1

1/

0.8

3.0

.3

10.5

15

10

66

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

3.4

 

12.6

15

11

76

 

208/230-3-60

Std

187

254

23.6

 

146

1

1/

1.4

5.2

.6

30.2/30.2

35/35

29/29

180/180

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

4

 

7.5

 

32.5/32.5

40/40

32/32

205/205

 

 

 

 

 

 

 

 

 

 

 

007

460-3-60

Std

414

508

10.6

 

73

1

1/

0.6

2.6

.3

15.4

20

15

90

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

4

 

3.4

 

16.1

20

16

103

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

8.5

 

58.4

1

1/

0.6

2.6

.3

12.3

15

13

72

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

4

 

3.4

 

12.9

20

14

82

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Full Load Amps

HACR —

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination

load equipment (refer to NEC Articles 430 and 440), the overcurrent

protective device for the unit shall be fuse or HACR breaker. Canadian

units may be fuse or circuit breaker.

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

=1371

3

=457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

2. Unbalanced 3-Phase Supply Voltage

% Voltage Imbalance = 100 x

7

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percent

of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the max- imum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

10

Page 10
Image 10
Carrier 48TF004-007 specifications Electrical Data, Supply Size, Type FLA, Rla Lra, Fla Mca Mocp† Lra

48TF004-007 specifications

The Carrier 48TF004-007 is part of the brand's renowned rooftop unit series, designed to deliver efficient, reliable performance for commercial applications. Ideal for spaces such as offices, retail stores, and small manufacturing facilities, these units encapsulate advanced technology to enhance indoor air quality and optimize climate control.

One of the standout features of the Carrier 48TF004-007 units is their variable speed compressor technology. This innovation not only allows for precise temperature control but also reduces energy consumption by modulating the compressor's speed according to the cooling or heating demand. By operating at lower speeds during less demanding conditions, these units significantly decrease energy usage compared to traditional single-speed compressors, contributing to lower utility bills and a reduced carbon footprint.

Energy efficiency is further enhanced with the inclusion of high-performance scroll compressors, which are known for their reliable operation and quiet performance. Coupled with an Energy Efficiency Ratio (EER) that meets or exceeds industry standards, these systems are designed to offer economical operation without sacrificing comfort.

Incorporating smart controls and connectivity features, the Carrier 48TF004-007 units allow for easy integration into building management systems (BMS). This enhances the ability to monitor and manage energy usage in real time, further promoting efficiency. The units are also compatible with various thermostat options, allowing for user-friendly operation and customization of settings.

Another significant characteristic of the Carrier 48TF004-007 is its durable construction. Built with galvanized steel and powder-coated finishes, these units are designed to withstand the rigors of outdoor installation, ensuring long-lasting performance even in harsh weather conditions. Additionally, the units come equipped with advanced filtration systems that help improve indoor air quality by effectively removing dust, allergens, and other particulate matter from the air.

Maintenance is simplified with the Carrier 48TF004-007, providing easy access to vital components, which supports reduced downtime and service costs. The units also feature low operating sound levels, making them suitable for noise-sensitive applications.

In conclusion, the Carrier 48TF004-007 rooftop units stand out for their energy efficiency, advanced technology, durability, and ease of maintenance, making them an excellent choice for any commercial space looking to enhance comfort while effectively managing operational costs.