Carrier 50CR installation instructions TroubleshootingChart, Continued next page

Models: 50CR

1 32
Download 32 pages 7.8 Kb
Page 30
Image 30
Table 7—Troubleshooting Chart

50CR

Table 7—Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

 

 

 

 

Power failure

Call power company

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

 

Defective contactor, transformer, control relay, defrost

Replace component

 

board, or high--pressure, loss--

 

of--charge or low--pressure switch

 

 

 

 

Compressor and outdoor fan

Insufficient line voltage

Determine cause and correct

 

 

will not start

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

 

 

 

 

 

User Interface setting too low/too high

Reset UI setting

 

 

 

 

 

DO NOT bypass this compressor time

 

Units have a 5--minute time delay

delay–wait for 5 minutes until time--delay

 

 

relay is de--energized

 

 

 

 

Faulty wiring or circuit

Check wiring and repair or replace

 

Loose connections in compressor

 

 

 

 

 

 

Compressor motor burned out, seized, or

Determine cause

Compressor will not start but condenser fan

internal overload open

Replace compressor

 

 

Defective run capacitor, overload, or PTC (positive

 

runs

Determine cause and replace

temperature coefficient) thermistor

 

 

 

 

 

 

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

 

Determine cause

 

 

 

 

 

 

Low input voltage (20 percent low)

Determine cause and correct

Three-phase scroll compressor (size 030-

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the

060 unit) has a low pressure differential

3--phase power leads to the unit

 

 

 

 

 

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

 

charge to capacities shown on rating plate

 

 

 

 

 

 

Defective compressor

Replace and determine cause

Compressor cycles (other than normally satis-

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

fying) cooling/heating calls

Defective run/start capacitor, overload or start relay

Determine cause and replace

 

 

Faulty outdoor fan motor or capacitor

Replace

 

Damaged reversing valve

Determine cause and correct

 

Restriction in refrigerant system

Locate restriction and remove

 

Dirty air filter

Replace filter

 

Unit undersized for load

Decrease load or increase unit size

 

UI temperature set too low/too high

Reset UI setting

 

Low refrigerant charge

Locate leak, repair, and recharge

Compressor operates continuously

 

Check defrost time settings

Frosted coil with incorrect defrost operation

Reset as necessary

 

Check defrost temperature switch

 

 

 

 

Replace as necessary

 

 

 

 

Air in system

Recover refrigerant, evacuate system, and re-

 

charge

 

 

 

 

 

 

Outdoor coil dirty or restricted

Clean coil or remove restriction

 

Dirty air filter

Replace filter

 

Dirty indoor or outdoor coil

Clean coil

 

Refrigerant overcharged

Recover excess refrigerant

Excessive head pressure

 

 

Air in system

Recover refrigerant, evacuate system, and re-

 

charge

 

 

 

 

 

 

(Heat) Indoor air restricted or recirculating

Determine cause and correct

 

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

(Continued next page)

30

Page 30
Image 30
Carrier 50CR installation instructions TroubleshootingChart, Continued next page