Table 7—Troubleshooting Chart (Cont’d)
SYMPTOM | CAUSE | REMEDY | |
|
|
| |
Head pressure too low | Low refrigerant charge | Check for leaks, repair and recharge | |
Restriction in liquid tube | Remove restriction | ||
| |||
| (Cool) High Heat load | Check for source and eliminate | |
Excessive suction pressure | Reversing valve hung up or leaking internally | Replace valve | |
| Refrigerant overcharged | Recover excess refrigerant | |
| (Cool) Dirty air filter | Replace filter | |
| (Heat) Outdoor coil frosted | Move timer on control board to 30 minutes between | |
| defrost cycles | ||
|
| ||
|
|
| |
| Low refrigerant charge | Check for leaks, repair and recharge | |
Suction pressure too low | Metering device or low side restricted | Remove source of restriction | |
(Cool) Insufficient coil airflow | Increase air quantity | ||
| |||
| Check | ||
|
| ||
|
|
| |
| (Cool) Temperature too low in conditioned area | Reset UI setting | |
| (Cool) Outdoor ambient below 55°F | Install | |
| Filter drier restricted | Replace | |
Compressor runs but outdoor fan does not | NC (normally closed) contacts on defrost board | Check condition of relay on board | |
open | Replace if necessary | ||
| |||
|
|
| |
| Blower wheel not secured to shaft | Properly tighten blower wheel to shaft | |
IFM does not run | Insufficient voltage at motor | Determine cause and correct | |
| Power connectors not properly sealed | Connectors should snap easily; do not force | |
| Water dripping into motor | Verify proper drip loops in connector wires | |
IFM operation is intermittent | Connectors not firmly sealed | Gently pull wires individually to be sure they are | |
| crimped into the housing | ||
|
|
50CR
31