Complete C |
Complete C1 |
Complete C
Complete C2
Complete C1 | Complete C2 |
BC | — Blower Contactor |
CB | — Circuit Breaker |
CC— Compressor Contactor
CO | — Sensor, Condensate Overflow |
DPP | — Dual Point Power |
FP1 | — Sensor, Water Coil Freeze Protection |
FP2 | — Sensor, Air Coil Freeze Protection |
HP | — |
HPWR | — |
JW3 | — Clippable Field Selection Jumper |
LOC | — Loss of Charge Pressure Switch |
PDB | — Power Distribution Block |
RVS | — Reversing Valve Solenoid |
TRANS | — Transformer |
TXV | — Thermostatic Expansion Valve |
| Factory Line Voltage Wiring |
| Factory Low Voltage Wiring |
LEGEND
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.O.
Relay Contacts - N.C.
Temperature Switch
Switch - Low Pressure
Switch - High Pressure
Wire Nut
NOTES:
1.Compressor and blower motor thermally protected internally.
2.All wiring to the unit must comply with NEC (National Electrical Code, U.S.A.) and local codes.
3.
4.FPI thermistor provides freeze protection for WATER. When using ANTIFREEZE solutions, cut JW3 jumper.
5.Typical heat pump thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring
must be “Class 1” and voltage rating equal to or greater than unit supply voltage.
6.
7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two stand- offs as shown.)
8.Suffix 1 designates association with lead compressor. Suffix 2 with lag compressor.
9.For dual point power (DPP) option, blower wire will connect to other PBD.
Fig. 12 — 50HQP072-120 Units — Typical Control Wiring with Complete C Control