Table 3A — Electrical Data — 50HQP072-120 Standard Units

Table 3B — Electrical Data — 50HQP072-120 Dual Point Power Units

LEGEND
*Time-delay fuse or HACR circuit breaker.

Table 4 — Low Voltage VA Ratings

* Standard transformer is 75 VA.
UNIT
50HQP
VOLTAGE
CODE VOLTAGE MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE
QTY RLA LRA
072 9 380/420-3-50 360/440 A,B,C 2 5.4 38.0 1.8 12.6 13.9 15
096 9 380/420-3-50 360/440 A,B,C 2 6.1 43.0 3.4 15.6 17.1 20
120 9 380/420-3-50 360/440 A,B,C 2 7.8 51.5 4.9 20.5 22.5 30
UNIT
50HQP
VOLTAGE
CODE VOLTAGE MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR EMERGENCY
POWER SUPPLY
QTY RLA LRA
Total
Comp
FLA
Comp
MCA
Comp
Max
Fuse
Fan
Motor
FLA
Fan
MCA
FAN
MAX
FUSE
072 9 380/420-3-50 360/440 A,B,C 2 5.4 38.0 10.8 12.2 15 1.8 2.3 15
096 9 380/420-3-50 360/440 A,B,C 2 6.1 43.0 12.2 13.7 15 3.4 4.3 15
120 9 380/420-3-50 360/440 A,B,C 2 7.8 51.5 15.6 17.6 25 4.9 6.1 15
FLA Full Load Amps
HACR Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
RLA Rated Load Amps
COMPONENTS IN UNIT VA
Typical Blower Contactor 6 - 9
Typical Reversing Valve Solenoid (2) 8 - 12
30A Compressor Contactor (2) 12 - 18
Complete C Board (2) 10 - 18
Deluxe D Board (2) 16 - 24
Remaining VA for Accessories*
Units with Complete C
Units with Deluxe D
18 - 39
12 - 33
NOTE: Low voltage connector may be removed for easy installation.

Fig. 16 — Low Voltage Field Wiring

Complete C 2Complete C 1

POWER

BLOCK

Fig. 17 — Line Voltage Wiring