Determine percent voltage imbalance.
= 0.95%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electri-
cal components.
NOTE: If more than 2% voltage imbalance is present, contact
local electric utility.
EXTERNAL LOOP POWER CONNECTION — If the unit
is to be connected to an external loop pump or flow controller,
connect the pump to the loop pump terminal block PB1. The
maximum power handling is 4 amps at 240 volts. The pumps
will automatically cycle as required by the unit.
420-VOLT OPERATION All 380/420 volt units are factory
wired for 380 volts. The transformers may be switched to
420-volt operation (as illustrated on the wiring diagram) by
disconnecting the VIO lead at L1 and attaching the BRN lead
to L1. Close open end of VIO lead.
% Voltage Imbalance = 100 x 4
421
Pressure-
Temperature
Plugs
Boiler
Drains
Strainer – Field-Installed Accessory
(16 to 20 mesh recommended for
filter sediment)
Shut-Off
Valve
Water
Control
Valve
Automatic
Balance Valve
Expansion
Tank
Water Out
Water In
From Pump
Fig. 11 — Typical Ground-Water Piping Installation
a50-8542