Determine percent voltage imbalance. % Voltage Imbalance = 100 x 4214
= 0.95%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.
NOTE: If more than 2% voltage imbalance is present, contact local electric utility.
EXTERNAL LOOP POWER CONNECTION — If the unit is to be connected to an external loop pump or flow controller, connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at 240 volts. The pumps will automatically cycle as required by the unit.
Water Automatic
Control Balance Valve
Valve
Boiler
Drains
Pressure-
Temperature
Plugs
Expansion
Tank
Water Out
Water In
From Pump
Valve
Strainer –
Fig. 11 — Typical Ground-Water Piping Installation