27
Filters — Filters must be clean for maximum performance.
Inspect filters every month under normal operating conditions.
replace when necessary.
Washable, high efficiency, electrostatic filters, when dirty,
can exhibit a very high pressure drop for the fan motor and re-
duce air flow, resulting in poor performance. It is especially im-
portant to provide consistent washing of these filters (in the op-
posite direction of the normal air flow) once per month using a
high pressure wash.
Water Coil — Keep all air out of the water coil. Check
open loop systems to be sure the well head is not allowing air
to infiltrate the water line. Always keep lines airtight.
DIRECT GROUND WATER APPLICATIONS — If the
system is installed in an area with a known high mineral con-
tent (125 ppm or greater) in the water, it is best to establish a
periodic maintenance schedule with the owner so the coil can
be checked regularly.
Should periodic coil cleaning be necessary, use standard
coil cleaning procedures, which are compatible with the heat
exchanger material and copper water lines. Generally, the more
water flowing through the unit, the less chance for scaling.
Therefore, 1.6 L/m per kW is recommended as a minimum
flow. Minimum flow rate for entering water temperatures be-
low 10.0 C is 2.2 L/m per kW.
ALL OTHER WATER LOOP APPLICATIONS — Gener-
ally, water coil maintenance is not needed for closed loop sys-
tems. However, if the piping is known to have high dirt or de-
bris content, it is best to establish a periodic maintenance
schedule with the owner so the water coil can be checked regu-
larly. Dirty installations are typically the result of deterioration
of iron or galvanized piping or components in the system.
Open cooling towers requiring heavy chemical treatment and
mineral buildup through water use can also contribute to higher
maintenance. Should periodic coil cleaning be necessary, use
standard coil cleaning procedures, which are compatible with
both the heat exchanger material and copper water lines. Gen-
erally, the more water flowing through the unit, the less chance
for scaling. However, flow rates over 3.9 L/m per kW can pro-
duce water (or debris) velocities that can erode the heat ex-
changer wall and ultimately produce leaks.
Condensate Drain Pans — Check condensate drain
pans for algae growth twice a year. If algae growth is apparent,
consult a water treatment specialist for proper chemical treat-
ment. The application of an algaecide every three months will
typically eliminate algae problems in most locations.
Refrigerant System — Verify air and water flow rates
are at proper levels before servicing. To maintain sealed circuit-
ry integrity, do not install service gages unless unit operation
appears abnormal.
Condensate Drain Cleaning — Clean the drain line
and unit drain pan at the start of each cooling season. Check
flow by pouring water into drain. Be sure trap is filled to main-
tain an air seal.
Air Coil Cleaning — Remove dirt and debris from evap-
orator coil as required by condition of the coil. Clean coil with
a stiff brush, vacuum cleaner, or compressed air. Use a fin
comb of the correct tooth spacing when straightening mashed
or bent coil fins.
Condenser Cleaning — Water-cooled condensers may
require cleaning of scale (water deposits) due to improperly
maintained closed-loop water systems. Sludge build-up may
need to be cleaned in an open water tower system due to
induced contaminants.
Local water conditions may cause excessive fouling or
pitting of tubes. Condenser tubes should therefore be cleaned at
least once a year, or more often if the water is contaminated.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment
analysis is recommended. Refer to the Carrier System Design
Manual, Part 5, for general water conditioning information.
Clean condensers with an inhibited hydrochloric acid solu-
tion. The acid can stain hands and clothing, damage concrete,
and, without inhibitor, damage steel. Cover surroundings to
guard against splashing. Vapors from vent pipe are not harmful,
but take care to prevent liquid from being carried over by the
gases.
Warm solution acts faster, but cold solution is just as effec-
tive if applied for a longer period.
GRAVITY FLOW METHOD Do not add solution faster
than vent can exhaust the generated gases.
When condenser is full, allow solution to remain overnight,
then drain condenser and flush with clean water. Follow acid
manufacturers instructions. See Fig. 22.
FORCED CIRCULATION METHOD — Fully open vent
pipe when filling condenser. The vent may be closed when
condenser is full and pump is operating. See Fig. 23.
Regulate flow to condenser with a supply line valve. If
pump is a nonoverloading type, the valve may be fully closed
while pump is running.
IMPORTANT: Units should never be operated with-
out a filter.
IMPORTANT: To avoid fouled machinery and extensive
unit clean-up, DO NOT operate units without filters in
place. DO NOT use equipment as a temporary heat source
during construction.
CAUTION
Follow all safety codes. Wear safety glasses and rubber
gloves when using inhibited hydrochloric acid solution.
Observe and follow acid manufacturers instructions. Fail-
ure to follow these safety precautions could result in per-
sonal injury or equipment or property damage.
Fig. 22 — Gravity Flow Method
FILL CONDENSER WITH
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
CHEMICAL ACTION.
PAIL
FUNNEL
CONDENSER
PAIL
1.0 TO 1.2 m
VENT
PIPE 1.5 m APPROX
1-IN.
(25 mm)
PIPE
a50-8586