Carrier NP034-074 specifications 8700

Models: NP034-074

1 72
Download 72 pages 11.58 Kb
Page 13
Image 13
8700

UNIT

SIZE

WEIGHT

 

A

 

B

 

C

 

D

 

E

 

F

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lb

kg

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

 

ft-in.

mm

 

ft-in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48DJD,DKD,NPD

 

8700

3946

5969

19-7

6717

22-07¤16

 

 

 

 

2718

8-11

6541

 

21-51¤2

 

 

 

48DJE,NPE

054

8820

4000

1163

3-913¤16

11,524

37-911¤16

 

11,140

 

36-69¤16

 

 

 

 

 

 

 

 

 

 

50DW,DY,NB

 

8250

3742

6045

19-10

7676

25-23¤16

 

 

 

 

2830

9-33¤4

6427

 

21-1

 

 

 

48DJD,DKD,NPD

 

9000

4082

5969

19-7

6717

22-07¤16

 

 

 

 

2718

8-11

6541

 

21-51¤2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48DJE,NPE

064

9120

4137

1163

3-913¤16

11,524

37-911¤16

11,140

 

36-69¤16

 

 

 

 

 

 

 

 

 

 

50DW,DY,NB

 

8550

3878

6045

19-10

7676

25-23¤16

 

 

 

 

2830

9-33¤4

6427

 

21-1

 

 

 

48DJD,DKD,NPD

 

9420

4273

6401

21-0

6717

22-07¤16

 

 

 

 

3543

11-71¤2

5715

 

18-9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48DJE,NPE

074

9550

4332

1163

3-913¤16

12,433

40-91¤2

12,049

 

39-63¤8

 

 

 

 

 

 

 

 

 

 

50DW,DY,NB

 

8970

4069

6477

21-3

7676

25-23¤16

 

 

 

 

3694

12-13¤4

5563

 

18-3

 

 

 

LEGEND

CONN Ð Connection

DIM Ð Dimension

*Dimension shown is for 48 series units. On 50 series units, dimension given is measured from economizer end of unit to drain connection closest to condenser fans.

NOTES:

1. Dimensions in [ ] are in millimeters.

2.Manual background Center of Gravity includes economizer. Unit weight does not include economizer.

3.Unit clearances:

Top Ð Do not restrict condenser fans Control Box End Ð 6 -0

Sides Ð 6 -0 (except power exhaust units 10 -0 )

Economizer End Ð 6 -0 (except power exhaust units 10 -0 )

For smaller service and operational clearances, contact Carrier Product Engineering Department.

4.Vertical discharge ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, support the ducts using cross braces as done on the accessory roof curb.

5.When unit is slab mounted, locate the condensate drain as low as possible on vertical face of base rail at the same location as the standard condensate drain (using factory supplied ®tting). Plug factory drilled condensate hole.

Fig. 4C Ð Base Unit Dimensional Drawing; 48DJ,DK,NP/50DW,DY,NB054-074 Units

13

Page 13
Image 13
Carrier NP034-074 specifications 8700