25% OUTDOOR-AIR DAMPER Ð See Manual Outdoor- Air Damper section on page 10 for adjustment details.

REFRIGERANT CHARGE Ð All units are shipped with a complete operating charge of R-22. See unit nameplate and Tables 1A and 1B for amount of charge. When adding a com- plete charge, evacuate system using standard evacuating pro- cedures and weigh in the speci®ed amount of charge. All units have charging charts for each refrigerant circuit. See Fig. 46-59.

PILOT LIGHT OFF (48NP Units Only) Ð If pilots do not light as described in Heating section on page 41, be sure that pilot ori®ce is unobstructed, then check for spark ignitor mal- functions as follows:

1.Turn off the control circuit breaker (CCB) to shut off con- trol supply power to ignitor control pack (ICP).

2.Check that spark gap is 3¤8 in. 6 1¤32 inch.

3.Check that ICP is securely grounded.

4.Check that the high-voltage lead is securely connected between the ICP and the electrode body.

5.Turn on CCB to restore power to ICP. Check that 24 v is supplied to terminal TH of the ICP.

6.Check unit label diagram for correct terminal usage if any wires are removed.