Carrier NP034-074 specifications Ð Air Quantity Limits cfm

Models: NP034-074

1 72
Download 72 pages 11.58 Kb
Page 40
Image 40
Table 10 Ð Air Quantity Limits (cfm)

Table 9B Ð Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units

 

 

 

 

 

 

 

 

 

 

 

BELTS

 

 

 

 

IFM

 

IFM

MOTOR PULLEY

BLOWER PULLEY

48 Series and 50 Series

 

50 Series

 

 

 

 

 

 

 

 

Horizontal Discharge Units

Vertical Discharge Units

Hp

 

RPM

 

 

 

 

 

 

 

 

 

No.

Type

Size (in.)

No.

Type

Size (in.)

Quantity

Type

Size (in.)

Quantity

 

Type

 

Size (in.)

 

 

 

Grooves

Grooves

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450

 

 

 

 

 

18.5

 

 

118

 

 

 

 

132

 

 

470

 

 

4.3

 

 

16.1

 

 

115

 

 

 

 

125

15

 

485

2

B5V

 

2

B5V

15.5

2

5VX

2

 

5VX

 

 

 

 

 

 

 

 

 

575

4.5

 

 

 

 

123

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650

 

 

5.1

 

 

13.7

 

 

112

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

725

 

 

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

405

 

 

 

 

 

18.5

 

 

123

 

 

 

 

132

 

 

470

3

 

4.3

3

 

16.1

3

 

118

3

 

 

 

125

20

 

485

 

B5V

 

 

B5V

15.5

 

5VX

 

 

5VX

 

 

 

 

 

 

 

 

 

 

 

 

575

 

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

660

2

 

5.1

2

 

13.7

2

 

115

2

 

 

 

123

 

 

725

 

 

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

405

 

 

 

 

 

18.5

 

 

123

 

 

 

 

132

 

 

470

3

 

4.3

3

 

16.1

3

5VX

 

3

 

 

 

125

25

 

485

 

B5V

 

 

B5V

15.5

 

 

 

 

 

5VX

 

 

 

575

 

4.5

 

 

 

 

115

 

 

 

123

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

2

 

5.5

2

 

13.7

2

B5V

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

725

 

 

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

470

4

 

4.3

4

 

16.1

4

 

 

4

 

 

 

 

 

 

485

 

 

15.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

530

3

B5V

4.7

3

B5V

15.5

3

5VX

118

3

 

5VX

 

123

 

600

 

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

660

2

 

5.9

2

 

15.5

2

 

 

2

 

 

 

 

 

 

730

 

 

6.5

 

 

 

 

 

 

 

 

 

 

 

IFM Ð

Indoor (Evaporator) Fan Motor

 

 

 

 

 

 

 

 

 

 

 

Check rotation of wheel with arrow on the fan housing. Check fan speed with a strobe-type tachometer, or use this formula:

Fan

=

motor rpm x motor sheave pitch diameter (in.)

Rpm

 

fan sheave pitch diameter (in.)

 

 

(Obtain motor rpm from the fan motor nameplate and read sheave pitch diameters marked on the fan and motor sheaves.)

Example:

 

Nameplate motor rpm

1760

Motor sheave pitch diameter (in.)

6.4

Fan sheave pitch diameter (in.)

12.4

Fan Rpm = 1760 x 6.4 = 908 Rpm 12.4

The maximum allowable fan speed for the supply-air fan is 900 rpm for 034 and 044 units and 750 rpm for 054-074 units. The maximum rpm for the power exhaust is 1300 rpm for 034 and 044 units and 925 rpm for 054-074 units. Excessive fan speed may result in condensate carryover from the evaporator coil, fan motor overload, or wheel failure. See Table 10 for Air Quantity Limits.

Table 10 Ð Air Quantity Limits (cfm)

UNIT SIZE

MINIMUM

MAXIMUM

034

6,000

15,000

044

8,000

20,000

054

10,000

25,000

064

12,000

30,000

074

14,000

30,000

Condenser Fans and Motors Ð Each unit has mul- tiple condenser fans and motors; these are positioned at the factory. See Fig. 32 for correct location of fan in ori®ce. Check that fan propeller rotation is correct; it should be counter- clockwise when facing the fans. If fan propeller rotation is incorrect, switch motor leads.

Return-Air Filters Ð Check that the correct ®lters are installed in the ®lter rack. See Tables 1A and 1B for quan- tities and sizes. Access is through the door marked FILTER SECTION. Do not operate the unit without return-air ®lters.

Economizer Inlet Screens Ð Check that they are in place before operating the unit.

Economizer Dampers Ð With no power to the unit, the economizer outdoor-air dampers should be fully closed. Check by opening the access door marked FILTER SEC- TION. On units with economizer, be sure economizer mini- mum position is set at the desired setting. Be sure hood is installed properly.

25% Outdoor-Air Damper Ð On units without econo- mizer, be sure 25% outdoor-air damper is set at the desired position. Also, be sure hood is installed properly.