Fig. 55 Ð Charging Chart, 054 Units; System 2,

Fig. 55 Ð Charging Chart, 054 Units; System 2,

All Condenser Fans Running

Fig. 56 Ð Charging Chart, 064 Units; System 1,

All Condenser Fans Running

Fig. 57 Ð Charging Chart, 064 Units; System 2,

All Condenser Fans Running

Fig. 58 Ð Charging Chart, 074 Units; System 1,

All Condenser Fans Running

Fig. 59 Ð Charging Chart, 074 Units; System 2,

All Condenser Fans Running

AUTOMATIC PILOT ADJUSTMENT (48 Series Units Only)

1.Set system selector switch at OFF position to shut off unit. Turn off power to unit.

2.Remove screw cap cover on pilot gas valve to expose adjusting screw.

3.To ensure that main burners do not ignite, remove wire from gas valve terminal 2. Tape wire. Do not allow wire to be grounded.

4.Turn on power to unit. Set system selector switch to HEAT position and set thermostat to a setting that will call for heat. Pilot ignites.

5.With a small screwdriver, turn adjustment screw until flame fully engulfs sensor.

6.Replace cap on pilot gas valve. Turn off power to unit. Return valve(s) to original position.

7.Check for proper burner operation by cycling the burn- ers. Wait 30 seconds between burner cycles.

8.Check that all panels are closed securely before leaving the unit.