Carrier NP034-074 specifications Ð Control Board Component Arrangement

Models: NP034-074

1 72
Download 72 pages 11.58 Kb
Page 54
Image 54
Fig. 64 Ð Control Board Component Arrangement

LEGEND

CLO Ð Compressor Lockout

PÐ Plug

SC Ð Safety Circuit

Fig. 64 Ð Control Board Component Arrangement

Symptom: Evaporator fan will not operate.

1.Turn unit power off and disconnect plug P1 from the con- trol board.

2.Install a jumper across Pin R and Pin G at plug P1 on the control board.

3.Turn unit power on and check if the indoor (evaporator) fan contactor (IFC) coil has been pulled in. If the con- tactor has not been pulled in, check the voltage across the IFC coil. If there is voltage at this point, the IFC con- tactor is defective. If there is no voltage, proceed to Step 4.

4.Turn unit power off and disconnect plug P4 from the con- trol board.

5.Turn unit power on and check for continuity across Pin 6 and Pin 3 at plug P4 on the control board. If there is no continuity, the board is defective. Replace control board. If there is continuity, then there is a bad con- nection between the board and plug P4. Correct the connection.

6.Turn unit power off. Reconnect plug P1 (if troubleshoot- ing is complete) and plug P4.

Symptom: Condenser fan no. 1 will not operate.

1.Turn unit power off. Disconnect plugs P1 and P3 from the control board.

2.Check for continuity between Pin 8 at plug P3 on the con- trol board and Pin Y1 at plug P1 on the control board. If there is no continuity, the board is defective. If there is continuity, either the connection is bad between plug P3 and the control board or the problem is external to the board. Reconnect plug P1 (if troubleshooting is com- plete) and plug P3 to the board.

Symptom: Condenser fan no. 2-5 will not operate.

1.Check operation of condenser fan no. 1. If fan no. 1 op- erates properly, the problem is external to the board.

Symptom: Compressor no. 1 will not operate.

1.Turn unit power off. Disconnect the 2 wires attached to the terminals marked SC1.

2.Check continuity between the 2 wires. If there is no continuity, the problem is external to the control board (possibly the pressure switches). If there is continuity, pro- ceed to Step 3.

3.Reconnect the wires removed in Step 1.

4.With the unit power still off, disconnect plug P1 from con- trol board. Install a jumper wire across Pin R and Pin Y1 at plug P1 on the control board.

5.Connect a voltmeter across the coil for compressor no. 1 contactor.

6.Energize unit and monitor the voltage for a few seconds.

IMPORTANT: Do not run compressor too long.

7.a. If proper voltage is indicated at the contactor, but con- tactor fails to close, replace contactor.

b.If voltage is indicated for a few seconds (i.e., the con- tactor momentarily pulls in and is then deenergized), the compressor lockout (CLO) logic has shut down the unit. This is an indication that the board is not sens- ing proper compressor current, or that one of the safe- ties has tripped. Proceed to Step 8 to verify compres- sor lockout logic operation.

54

Page 54
Image 54
Carrier NP034-074 specifications Ð Control Board Component Arrangement