Table 1B Ð Physical Data; 054-074 Units

BASE UNIT*

054

 

 

064

 

 

074

NOMINAL CAPACITY (tons)

 

50

 

 

 

60

 

 

 

75

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

48 Series, Low Heat

8700

 

 

9000

 

 

9420

48 Series, High Heat

8820

 

 

9120

 

 

9550

50 Series, Horizontal Discharge

8250

 

 

8550

 

 

8970

50 Series, Vertical Discharge

7700

 

 

8000

 

 

8430

With Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

48 Series, Low Heat

9230

 

 

9530

 

 

9950

48 Series, High Heat

9350

 

 

9650

 

 

10,080

50 Series, Horizontal Discharge

8780

 

 

9080

 

 

9500

50 Series, Vertical Discharge

8230

 

 

8530

 

 

8960

COMPRESSORS

 

 

 

 

 

Semi-Hermetic

 

 

 

 

Quantity...Type

2...06E

 

 

2...06E

 

 

2...06E

Capacity Steps (%)

20, 40, 60, 80, 100

 

 

17, 33, 50, 66, 83, 100

 

14, 28, 43, 71, 85, 100

Number of Refrigerant Circuits

 

2

 

 

 

2

 

 

 

2

REFRIGERANT

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Charge (lb), Sys 1/Sys 2

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Hot Gas Bypass

59.0/44.5

 

 

61.0/61.0

 

 

70.5/64.5

With Hot Gas Bypass

62.0/44.5

 

 

64.0/61.0

 

 

73.5/64.5

CONDENSER COILS

 

 

 

 

 

3¤8-in. Tube Diameter

 

 

 

 

Quantity

 

4

 

 

 

4

 

 

 

4

Rows...Fins/in.

 

 

 

 

 

 

 

 

 

 

 

 

 

Aluminum

2...17.0, 3...17.0

 

 

3...17.0

 

 

3...17.0

Copper (Optional)

2...15.7, 3...15.7

 

 

3...15.7

 

 

3...15.7

Total Face Area (sq ft)

72.4

 

 

72.4

 

 

108.4

EVAPORATOR COILS

 

 

 

 

 

1¤2-in. Tube Diameter

 

 

 

 

Quantity

 

2

 

 

 

2

 

 

 

2

Rows...Fins/in.

3...17.0

 

 

4...17.0

 

 

4...17.0

Total Face Area (sq ft)

61.5

 

 

61.5

 

 

61.5

Refrigerant Feed Device...

TXV...2

 

 

TXV...2

 

 

TXV..2

No. per Circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING SECTION (48 Series Units Only)

Low Heat

 

High Heat

 

Low Heat

 

High Heat

 

Low Heat

 

High Heat

Number of Heat Exchangers

12

 

18

 

 

12

 

18

 

 

12

 

18

Input (MBtuh)

540

 

810

 

 

540

 

810

 

 

540

 

810

Output (MBtuh)

432

 

648

 

 

432

 

648

 

 

432

 

648

Temperature Rise Range (F)

5-35

 

15-45

 

5-35

 

15-45

 

 

5-35

 

15-45

Efficiency (%)

80

 

80

 

 

80

 

80

 

 

80

 

80

Burner Ori®ce Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity (in. ...drill no.)

12 (.1285...30)

 

18 (.1285...30)

 

12 (.1285...30)

 

18 (.1285...30)

 

12 (.1285...30)

 

18 (.1285...30)

Pilot Ori®ce Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity (in. ...drill no.)

2 (.076...48)

 

3 (.076...48)

 

2 (.076...48)

 

3 (.076...48)

 

2 (.076...48)

 

3 (.076...48)

Firing Stages

2

 

2

 

 

2

 

2

 

 

2

 

2

Number of Gas Valves

2

 

3

 

 

2

 

3

 

 

2

 

3

CONDENSER FANS

 

 

 

 

 

Propeller Type

 

 

 

 

Quantity...Diameter (in.)

 

4...30

 

 

4...30

 

 

5...30

Nominal Cfm

 

40,000

 

 

40,000

 

 

50,000

Motor Hp...Rpm

1.0...1140

 

 

1.0...1140

 

 

1.0...1140

EVAPORATOR FAN

 

 

 

 

 

Centrifugal 30 x 27 in.

 

 

 

 

Nominal Cfm

 

17,500

 

 

21,000

 

 

24,500

Maximum Allowable Cfm

 

25,000

 

 

30,000

 

 

30,000

Maximum Allowable Rpm

 

750

 

 

750

 

 

750

Shaft Diameter at Pulley (in.)

 

111¤16

 

 

111¤16

 

 

111¤16

EVAPORATOR-FAN MOTOR AND DRIVE

 

 

 

 

 

(Any motor available on any unit)

 

 

 

 

Motor Hp

15.0

 

 

20.0

 

25.0

 

 

30.0

Motor Frame Size

254T

 

 

256T

 

284T

 

 

286T

Efficiency at Full Load (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Efficiency

84.5

 

 

87.5

 

87.1

 

 

88.3

High Efficiency²

90.0

 

 

91.0

 

91.7

 

 

92.4

Fan Pulley Pitch Diameter (in.)

13.7

 

 

13.7

 

13.7

 

 

15.5

Motor Pulley Pitch Diameter (in.)

4.5

 

 

 

5.1

 

5.5

 

 

 

5.9

Resulting Fan Rpm

555

 

 

625

 

660

 

 

700

Belts Quantity...Model No.

 

 

 

 

 

 

 

 

 

 

 

 

 

48 Series and 50 Series, Horizontal Discharge

2...5VX1120

 

 

2...5VX1150

 

2...5VX1150

 

 

2...5VX1180

50 Series, Vertical Discharge

2...5VX1230

 

 

2...5VX1230

 

2...5VX1230

 

 

2...5VX1230

Center Distance Range (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

48 Series and 50 Series, Horizontal Discharge

48.25...44.00

 

 

48.25...44.00

 

48.50...44.25

 

 

48.50...44.25

50 Series, Vertical Discharge

44.25...39.75

 

 

44.25...39.75

 

44.00...40.00

 

 

44.00...40.00

OPTIONAL POWER EXHAUST

 

 

Centrifugal, 18 x 15 in. (Any motor available on any unit)

 

 

Quantity...Motor Hp

2...5.0

 

 

2...7.5

 

 

2...10.0

Motor Frame Size

184T

 

 

213T

 

 

215T

Efficiency at Full Load (%)

84.0

 

 

82.9

 

 

85.6

Fan Pulley Pitch Diameter (in.)

10.6

 

 

10.6

 

 

10.6

Motor Pulley Pitch Diameter (in.)

 

4.5

 

 

 

5.0

 

 

 

5.6

Shaft Diameter at Pulley (in.)

17¤16

 

 

17¤16

 

 

17¤16

Resulting Fan Rpm

740

 

 

820

 

 

920

Maximum Allowable Rpm

925

 

 

925

 

 

925

FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Efficiency

 

 

 

 

 

 

 

 

 

 

 

 

 

Throwaway (Standard)

15...20 x 25 x 2

 

 

15...20 x 25 x 2

 

 

15...20 x 25 x 2

Quantity...Size (in.)

5...16 x 20 x 2

 

 

5...16 x 20 x 2

 

 

5...16 x 20 x 2

Medium Ef®ciency (30%) Pleated (Optional)

15...20 x 25 x 2

 

 

15...20 x 25 x 2

 

 

15...20 x 25 x 2

Quantity...Size (in.)

5...16 x 20 x 2

 

 

5...16 x 20 x 2

 

 

5...16 x 20 x 2

High Efficiency (90%) Bag Filters

 

 

 

 

 

 

 

 

 

 

 

 

 

with Pre®lters (Optional)

6...20 x 24 x 22

 

 

6...20 x 24 x 22

 

 

6...20 x 24 x 22

Quantity...Size (in.)

6...24 x 24 x 22

 

 

6...24 x 24 x 22

 

 

6...24 x 24 x 22

TXV Ð Thermostatic Expansion Valve

*Data is for all 48 and 50 Series units of the size listed unless otherwise speci®ed. ²Not available on 575-v units.

5

Page 5
Image 5
Carrier NP034-074 specifications Ð Physical Data 054-074 Units

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.