CONTENTS (cont)

·AUTOMATIC PILOT ADJUSTMENT (48 Series Units Only)

·GAS VALVE ADJUSTMENT (48 Series Units Only)

·MAIN BURNER ADJUSTMENT (48 Series

Units Only)

Main Burner Removal (48 Series Units Only) . . 50

Switch Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 50

Refrigerant Feed Components . . . . . . . . . . . . . . . 50

Thermostatic Expansion Valve (TXV) . . . . . . . . . 50

Moisture/Liquid Indicator . . . . . . . . . . . . . . . . . . . . 51

Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Liquid Line Service Valve . . . . . . . . . . . . . . . . . . . . 51

Compressor Discharge Service Valve . . . . . . . . 51

Compressor Suction Service Valve . . . . . . . . . . . 51

Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . 51

·COMPRESSOR PROTECTION

·EVAPORATOR-FAN MOTOR PROTECTION

·CONDENSER-FAN MOTOR PROTECTION

·HIGH- AND LOW-PRESSURE SWITCHES

Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Control Circuit, 115 V . . . . . . . . . . . . . . . . . . . . . . . 52

Control Circuit, 24 v . . . . . . . . . . . . . . . . . . . . . . . . . 52

Electric Heat (50 Series Units Only) . . . . . . . . . . 52

·OVERCURRENT

·OVERTEMPERATURE

Gas Heat (48 Series Units Only) . . . . . . . . . . . . . . 52

·LIMIT SWITCHES

·ROLLOUT SWITCH

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 52-69 Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

·ECONOMIZER MOTOR CHECKOUT

·ECONOMIZER CONTROL BOARD CHECKOUT

Unit Control Board Checkout . . . . . . . . . . . . . . . . 53

·BASIC CHECK

·DETAILED CHECK

START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1

GENERAL

This installation instruction contains base unit installa- tion, start-up, and service instructions only. For complete in- formation on PIC (Product Integrated Controls) and variable- air volume (VAV) controls and troubleshooting, refer to appropriate Controls and Troubleshooting literature also en- closed in this literature packet.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com- ponents. Only trained and quali®ed service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func- tions of cleaning coils and ®lters and replacing ®lters. All other operations should be performed by trained service per- sonnel. When working on air-conditioning equipment, ob- serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes, including ANSI (American Na- tional Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have ®re extinguisher available for all brazing operations.

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

Do not try to light any appliance. Do not touch any elec- trical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you can- not reach your gas supplier, call the ®re department.

Do not store or use gasoline or other ¯ammable vapors and liquids in the vicinity of this or any other appliance.

Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Re- fer to this manual. For assistance or additional infor- mation, consult a quali®ed installer, service agency, or the gas supplier.

Disconnect gas piping from 48 Series units when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pres- sure greater than 0.5 psig, it must be replaced. When pressure testing ®eld-supplied gas piping at pressures of

0.5psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.

INSTALLATION

Rigging and Unit Placement Ð Inspect unit for trans- portation damage. File claim with transportation agency. Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Sheets of plywood placed along the condenser coils will provide additional protection. All lifting lugs MUST be used when lifting unit. Level by using unit frame as a reference. See Fig. 1 for information. Unit and accessory weights are shown in Tables 1A, 1B, and 2. Weight distribution and center of gravity can be found in Fig. 2.

Roof Curb Ð Assemble and install as described in in- structions shipped with the accessory. Accessory roof curb and information required to ®eld fabricate a roof curb is shown in Fig. 3A-3C. Install insulation, cant strips, roo®ng and counter ¯ashing as required. For unit condensate drains to function properly, curb must be level or within tolerances shown in Fig. 3A-3C.

Roof Mount Ð Check building codes for weight distri- bution requirements. Unit weight is shown in Tables 1A and 1B. Unit may be mounted on class A, B, or C roo®ng material.

Slab Mount Ð Provide a level concrete slab that ex- tends beyond unit cabinet at least 6 inches. Make a slab 8 in. thick with 4 in. above grade. Use gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob- structing air¯ow.

2

Page 2
Image 2
Carrier NP034-074 specifications Contents, General

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.