Carrier NP034-074 specifications Ð Rigging Label

Models: NP034-074

1 72
Download 72 pages 11.58 Kb
Page 3
Image 3
Fig. 1 Ð Rigging Label

NOTES:

1.Sizes 034,044: Rig with 4 cables and spread with two 95 in. (2413 mm) and 2 A 1 A long spreader bars.

Sizes 054-074: Rig with 4 cables and spread with four 95 in. (2413 mm) and 2 A 1 B 1 A long spreader bars.

2.Center of gravity includes economizer.

1.All panels must be in place when rigging.

2.Unit is not designed for handling by forklift truck.

RIGGING WEIGHTS AND DIMENSIONS

UNIT

UNIT WEIGHT*

A

 

 

B

Lb

Kg

in.

 

mm

in.

 

mm

 

 

 

48DJD,DKD,NPD034

5941

2694.8

86.0

 

2185

109.4

 

2780

48DJE,NPE034

6070

2753.4

 

110.4

 

2804

 

 

 

 

48DJD,DKD,NPD044

6841

3103.1

92.6

 

2353

127.6

 

3240

48DJE,NPE044

6970

3161.6

 

128.6

 

3267

 

 

 

 

48DJD,DKD,NPD054

9230

4186.7

 

 

 

 

 

 

48DJE,NPE054

9350

4241.2

121.5

 

3086

126.8

 

3221

48DJD,DKD,NPD064

9530

4322.8

 

 

 

 

 

 

 

 

48DJE,NPE064

9650

4377.2

 

 

 

 

 

 

48DJD,DKD,NPD074

9950

4513.3

134.7

 

3421

134.7

 

3421

48DJE,NPE074

10,080

4572.3

 

 

 

 

 

 

 

 

50DJ,DK,NP034

5700

2585.5

84.8

 

2153

120.8

 

3067

50DW,DY,NB034

6270

2844.1

76.4

 

1940

102.5

 

2604

50DJ,DK,NP044

6350

2880.4

92.6

 

2353

126.6

 

3216

50DW,DY,NB044

6920

3138.9

86.0

 

2185

108.4

 

2753

50DJ,DK,NP054

8230

3733.1

120.8

 

3066

126.8

 

3221

50DW,DY,NB054

8780

3982.6

109.0

 

2769

109.0

 

2769

50DJ,DK,NP064

8530

3869.2

120.9

 

3071

120.9

 

3071

50DW,DY,NB064

9080

4119.7

120.8

 

3066

126.8

 

3221

50DJ,DK,NP074

8960

4064.3

131.7

 

3345

137.6

 

3495

50DW,DY,NB074

9500

4309.2

109.0

 

2769

109.0

 

2769

*Includes optional economizer.

Fig. 1 Ð Rigging Label

If roof curb is not used, support unit with steel beams along its entire length and then support steel as required. As a mini- mum, unit must be supported across its width at each lifting lug location.

Positioning Ð Provide clearance around and above unit for air¯ow, safety, and service access. Do not restrict top (area above condenser fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service.

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

On units equipped with or power exhaust option, high ve- locity air is exhausted out the hoods. Unit should be posi- tioned with at least 10 ft clearance between the exhaust hoods and any obstruction. Although unit is weatherproof, guard against water from higher level runoff and overhangs.

3

Page 3
Image 3